LRUZ Rafter Hanger - Simpson Strong-Tie

Solid Sawn Lumber Connectors
Solid Sawn Lumber Connectors
LRUZ Rafter Hanger
The LRUZ offers an economic alternative for those
applications requiring a sloped hanger for rafter-to-ridge
connections. Used with solid-sawn rafters, the LRUZ’s unique
design enables the hanger to be installed either before or
after the rafter is in place. The field-adjustable seat helps
improve job efficiency by eliminating mismatched angles in
the field and lead times associated with special orders. The
LRUZ offers comparable or better load capacity to other
rafter hangers at a reduced cost while using fewer fasteners.
FEATURES:
• The open design and ability to field-adjust the
slope makes the LRUZ ideal for both retrofit or
new applications
• Accommodates roof pitches from 0:12 to 14:12
• Slopes up or down to 45°. For slopes greater
than 45° to 49° (14:12), allowable loads are 0.85
of table loads
• For added versatility, the fasteners on the face
of the hanger are placed high enabling the bottom
of the rafter to hang below the ridge beam
(see “Max. C1” dimension)
• Can be installed using nails or Simpson Strong-Tie ®
Strong-Drive ® SD Connector screws
MATERIAL: 18 gauge
FINISH: ZMAX® coating
INSTALLATION:
•
Use all specified fasteners. See General Notes.
• Joist fasteners must be installed at an angle
through the rafter or joist into the header to achieve
the table loads.
• See alternate installation on page 86 for retrofit
applications.
H
B
LRU28Z
Typical
LRUZ Installation
(Other models
similar)
W
Dome Double
Shear Nailing
Side View
Double
Shear
Nailing
Top View
U.S. Patent 5,603,580
These products are approved for installation with the Strong-Drive ® SD Connector screw. See page 24 for more information.
Standard Installation 1,2,3
Factored Resistance
Model
No.
LRU26Z
LRU28Z
LRU210Z
LRU212Z
92
Fasteners 4,5
W
H
B
Max
C1
15⁄8
5¼
115⁄16
1¾
15⁄8
15⁄8
15⁄8
615⁄16
8 3⁄16
10 11⁄16
115⁄16
1 15⁄16
1 15⁄16
D.Fir-L
Header
Joist
4-10d
5-10d
4-16d
5-16d
6-10d
5-10d
6-16d
5-16d
6-10d
7-10d
6-16d
7-16d
6-10d
7-10d
6-16d
7-16d
2 5⁄8
1 3⁄4
3 1⁄2
Uplift
(K D = 1.15)
lbs
kN
945
4.20
1130
5.03
1180
5.25
1180
5.25
1610
7.16
1610
7.16
1910
8.50
1910
8.50
Normal
(K D = 1.00)
lbs
kN
1360
6.05
1985
8.83
1360
6.05
1985
8.83
2095
9.32
2375
10.56
2095
9.32
2805
12.48
S-P-F
Uplift
(K D = 1.15)
lbs
kN
670
2.98
800
3.56
840
3.74
840
3.74
1145
5.09
1145
5.09
1355
6.03
1355
6.03
1.Factored uplift resistances have been increased 15% for wind or earthquake loading; no further increase is allowed.
Reduce where other load durations govern.
2.Factored resistances shown are applicable for roof slopes up to and including 45° (12:12).
For roof slopes greater than 45° up to and including 49° (14:12) multiply the tabulated resistances by 0.85.
3.LRUZ’s may be installed using Strong-Drive ® SD#10x1½" Connector screws into the header and Strong-Drive SD#10x2½" Connector screws
into the joist at full 16d capacity.
4.For single 2x headers, use 10dx1½" nails into the header and 10d commons into the joist.
Multiply the tablulated 10d capadity x 0.77. Alternately, install Strong-Drive SD Connector screws (see footnote 3 above).
5.For alternate installation under retrofit applications, Strong-Drive SD#10x2½" Connector screws may be installed sloped upwards to match
the roof slope (45° max). Multiply the tabulated 16d values x 0.73. See Alternate Installation for Retrofit Applications detail on page 93.
6.NAILS: 16d = 0.162" dia. x 3½" long, 10d = 0.148" dia. x 3" long; 10dx1½ = 0.148" dia. x 1½" long. See pages 22-23 for other nail sizes and information.
7.SCREWS: SD#10x2½" (SD10212) = 0.161" dia. x 2½" long; SD#10x1½" (SD10112) = 0.161" dia. x 1½" long.
Normal
(K D = 1.00)
lbs
kN
965
4.29
1410
6.27
965
4.29
1410
6.27
1485
6.61
1685
7.50
1485
6.61
1990
8.85
Catalogue C-C-CAN2015 © 2015 SIMPSON STRONG-TIE COMPANY INC.
Dimensions (in.)
Solid Sawn Lumber Connectors
LRUZ
Rafter Hanger
Alternate Installation for Retrofit Applications
When an existing roof deck prevents the horizontal installation of fasteners, Strong-Drive® SD #10x2 1⁄2"
Connector screws may be installed sloped upward to match the roof pitch (45° max.). Use table values
for an installation with 16d nails x 0.73 (see footnote 5) when SD screws are sloped. Nails may not be
installed sloped upward.
Existing
roof deck
Minimum Ridge Beam Depth (in inches)
Roof
Pitch
Match
roof pitch
(45° max.)
LRU26
LRU28
LRU210
LRU212
Rafter Size
Rafter Size
Rafter Size
Rafter Size
2x8
2x6
2x8
2x10
2x8
2x10
2x12
2x10
2x12
2:12
7
3 ⁄8
5
5 ⁄8
—
1
5 ⁄2
1
7 ⁄4
—
5
7 ⁄8
5
9 ⁄8
—
9 1⁄4
3:12
3 ⁄8
3
5 ⁄4
—
5 ⁄2
1
7 ⁄4
—
7 ⁄4
7
9 ⁄8
—
9 1⁄4
7
1
3
4:12
4 5 7⁄8
—
5 1⁄2
7 1⁄4
—
8 10 1⁄8
—
9 1⁄4
5:12
4 1⁄4
6 1⁄8
—
5 1⁄2
7 3⁄8
—
8 1⁄4
10 1⁄2
—
9 1⁄4
6:12
3
4 ⁄8
3
6 ⁄8
—
1
5 ⁄2
3
7 ⁄4
—
5
8 ⁄8
10 ⁄8
—
9 1⁄4
7:12
4 5⁄8
6 5⁄8
—
5 3⁄4
8 1⁄8
6 5⁄8
9 11 1⁄4
—
9 1⁄2
7
8:12
4 7⁄8
7 —
6 1⁄8
8 1⁄2
7 9 3⁄8
11 3⁄4
7 5⁄8
10 9:12
5 1⁄8
7 3⁄8
—
6 1⁄2
9 7 3⁄8
9 7⁄8
12 3⁄8
8 1⁄8
10 5⁄8
10:12
5 3⁄8
7 3⁄4
4 1⁄2
6 7⁄8
9 3⁄8
7 3⁄4
10 1⁄4
12 7⁄8
8 1⁄2
11 1⁄8
11:12
3
5 ⁄4
1
8 ⁄8
7
4 ⁄8
1
7 ⁄4
7
9 ⁄8
1
8 ⁄8
10 ⁄4
13 ⁄2
9 11 3⁄4
12:12
6 8 1⁄2
5 1⁄8
7 5⁄8
10 1⁄2
8 1⁄2
11 3⁄8
14 1⁄8
9 5⁄8
12 3⁄8
13:12
6 3⁄8
9 5 1⁄2
8 1⁄8
11 1⁄8
9 12 14 7⁄8
10 1⁄4
13 1⁄8
14:12
6 ⁄4
9 ⁄2
5 ⁄8
8 ⁄8
11 ⁄8
9 ⁄2
12 ⁄2
15 ⁄8
10 ⁄4
13 ⁄8
3
1
7
5
5
1
3
1
1
5
3
Alternate Installation for
Retrofit Applications
Ridge
Beam
Depth
Solid Sawn Lumber Connectors
2x6
LRU
H
7
1.Minimum ridge beam depths shown assume rafter and ridge beam are flush at the top.
2.Minimum ridge beam depths have been determined to ensure the Max C1 dimension for the LRU is not exceeded.
Deeper ridge beams may be required to support the rafter loads as determined by the Designer.
C1
Installation on
Minimum Depth Beam
Catalogue C-C-CAN2015 © 2015 SIMPSON STRONG-TIE COMPANY INC.
HH Header Hangers
For fast, accurate installation of door and window headers and other cross
members. HH header hangers can speed up the job, strengthen the frame, and
eliminate the need for trimmers.
MATERIAL: 16 gauge FINISH: Galvanized
INSTALLATION: • Use all specified fasteners. See General Notes.
• Attachment to 2x studs will result in two round holes not being filled
in the studs and reduction in capacity. See table for capacities and
nailing requirements.
Dimensions
(in)
Model
No.
HH4
W
3 1⁄2
H
2 13⁄16
Fasteners
Post
Size
7-10dx1 1⁄2 4-10dx1 1⁄2
2-2x
7-16dx2 1⁄2 4-16dx2 1⁄2
2x
5 1⁄2
5 1⁄8
Header
2x
4x
HH6
Post
9-16d
4-16d
10-10dx1 1⁄2 6-10dx1 1⁄2
2-2x 10-16dx2 1⁄2 6-16dx2 1⁄2
4x
12-16d
6-16d
311/16"
W
HH4
Factored Resistance
D.Fir-L
F2
F3
F4
F1
F1
(K D = 1.00)
(K D = 1.15)
(K D = 1.00)
lbs
lbs
lbs
lbs
lbs
kN
kN
kN
kN
kN
1240
—
890 1370
1125
5.52
— 3.96 6.09
5.00
1715
— 1125 1410
1580
7.63
— 5.00 6.27
7.03
2205
1125 1125 2140
2035
9.81
5.00 5.00 9.52
9.05
1930
— 1330 1930
1585
8.59
— 5.92 8.59
7.05
2450
— 1690 2405
2260
10.90
—
7.52 10.70
10.05
2940
1690 1690 2405
2710
13.08
7.52 7.52 10.70
12.06
1½"
S-P-F
F2
F3
F4
(K D = 1.15)
lbs
lbs
lbs
kN
kN
kN
—
765 970
— 3.40 4.31
—
965 1000
— 4.29 4.45
1040 965 1520
4.63 4.29 6.76
— 1155 1370
—
5.14 6.09
— 1480 1705
— 6.58 7.58
1370 1510 1705
6.09 6.72 7.58
HH Load
Directions
Typical HH
Installation
1.F 2, F 3 and F4 factored resistances have been increased 15% for earthquake or wind loading; no further increase is allowed.
2.NAILS: 16d = 0.162" dia. x 3 1⁄2" long. See pages 22-23 for other nail sizes and information.