23BI61 Data Sheet


RTU511
Data Sheet
Binary Input 23BI61
Binary Input 23BI61
Note for 23BI61 R0002: Due to thermal
conditions in the range 110 – 126,5 V DC
only 50% (or less) of the inputs may have
active signals at the same time.
Example: I1, I3, I5, I7, …
or: I2, I4, I6, I8, …
Application
The binary input board 23BI61 is used for the
isolated input of up to 16 binary process
signals. Scanning and processing of the inputs
are executed with the high time resolution of 1
ms. Allocation of an input to a processing
function can be done according to the rules of
configuration. The board 23BI61 can process
the following types of signals:





16 single indications with time stamp
8 double indications with time stamp
2 digital measured values with 8 bit
1 digital measured value with 16 bit
16 pulse counters values
Characteristics
Fig. 1: Block diagram
Binary input board 23BI61
Eight inputs are building a group with common
return. The inputs are potentially isolated by
means of opto-couplers.
The binary input board 23BI61 is available in
two versions (Rubric):

24 … 48 V DC
23BI61 R0001

60 … 110 V DC
23BI61 R0002
The board has sixteen light emitting diodes to
indicate the signal-state. The LED follows
directly the input.
The maximum permissible
counter pulses is 25 Hz.
frequency
Doc. No.: 1KGT 150 831 V000 1
for
1

RTU511
Data Sheet
Binary Input 23BI61
The binary input board 23BI61 can execute the
following processing functions for the different
types of signals:






Digital filtering to suppress contact
bounce
Suppression of technologically
caused chattering signals
Consistency check for all binary
input Intermediate position
suppression and monitoring for
double indications
Channels allocated to digital
measured values
Summation of increment pulses to
form counter values in 31 bit
counter value registers
Relocation of counter values into
other relocation registers on
request
The micro-controller on the board processes all
time-critical tasks of the parameterized
processing functions. Moreover it carries out
the interactive communication with the RTU
system bus. All configuration data and
processing parameters are loaded from the
communication unit via the RTU system bus.
The board is equipped with a serial interface to
the RTU system bus (Wired OR-Bus). While
using the binary input board in an RTU560 rack
configuration, it is necessary to connect one I/O
adaptor board 23AD64 to the first binary input
board 23BI61.
During initialization and operation the board
carries out a number of tests. If a fault occurs it
is reported to the communication unit. All fault
conditions impairing the function of the board
are displayed as common fault signal with a red
light emitting diode (LED). A failure of the board
is detected by the communication unit.
The 23BI61 board has a buffer which allows the
temporary storage of 50 time-stamped event
messages in chronological order designated for
transmission to the communication unit.
2
Doc. No.: 1KGT 150 831 V000 1

RTU511
Data Sheet
Binary Input 23BI61
Technical Data
In addition to the RTU500 series general technical data, the following applies:
Immunity Test
Input Channels
Inputs
16 channels, in two groups
of 8 with common return
Input voltage
24 … 48 V DC, +15 %
60 … 110 V DC, +15 %
Input current
Typically. 3-5 mA
for 24 … 110 V DC
Logical ‘1’
≥ 18 V @ 24 … 48 V DC
definitely detected ≥ 45 V @ 60 … 110 V DC
Current Consumption
5 Volt
40 mA
15 Volt
-
18 Volt
-
24 Volt
-
Mechanical Layout
Length
105.0 mm
Width
107.5 mm
Height
20.0 mm
Connection Type
Process
Connector
Removable Screw
Terminals
Electrostatic
Discharge
Immunity Test
IEC 61000-4-2
(level 3)
Radiated RadioFrequency
Electromagnetic
Field Immunity
Test
IEC 61000-4-3
(level 3)
Immunity to
Electrical Fast
Transient / Burst
IEC 61000-4-4
(level 3)
Surge Immunity
Test
IEC 61000-4-5
(level 3)
Immunity to
Conducted
Disturbances,
induced by RadioFrequency Fields
IEC 61000-4-6
(level 3)
AC Test Voltage
EN 61000-4-16
IEC 60870-2-1
(class VW3)
Impulse Voltage
withstand test
IEC 60255-5
IEC 60870-2-1
(class VW 3)
2,5 kV, 50 Hz
Test duration: 1 min
Performance criteria A
10 V/m
Performance criteria A
2 kV
Performance criteria A
2 kV
Performance criteria A
10 V
Performance criteria A
Environmental conditions
Temperature
Test Voltage
4 kV Contact
8 kV Air
-25 ... +70 C
Relative Humidity 5 ... 95 %
(non condensing)
Ordering Information
5 kV (1,2 / 50 µs)
Doc. No.: 1KGT 150 831 V000 1
23BI61 R0001
1KGT 014300R0001
23BI61 R0002
1KGT 014300R0002
3

RTU511
Data Sheet
Binary Input 23BI61
Note:
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard to
purchase orders, the agreed particulars shall prevail. ABB AG does
not accept any
responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents - in whole or in parts –is forbidden
without prior written consent of ABB AG.
Copyright© 2013 ABB
All rights reserved
4
Doc no.: 1KGT 150 831 V000 1