National Center for Supercomputing Applications Building No. 564 July, 2011 National Center for Supercomputing Applications Building Systems Manual Revision Log This page is intended to be used to record revisions as they are made to this static manual. Such revisions are included in the digital “live” document at the time they are included in this manual. Rev. No. 0 Revision By Whom Company / Dept. Building Systems Manual issued (Aug 2011) D. McFall RCx Team National Center for Supercomputing Applications Foreword The Systems Manual is meant to inform facilities staff, route mechanics, current or potential service contractors, as well as facility occupants and users as to the basis for operating and maintaining the facility’s systems to reduce energy consumption and provide a better work environment now. It is intended to be useful in the day-to-day operations of this facility. It also forms the essential basis of transferring important ‘system knowledge’ from one party to the next. The following information is encouraged to be included in this manual: • • • • • • • • • • • • • • • • General facility description with the locations of major equipment (new and old). A definition of current facility objectives, functional uses, special services including emergency response and desired level of control including any energy efficiency or load management priorities (design intent). Operating standards or procedures for major use and critical space/special needs areas including indoor environmental quality requirements and occupancy requirements and schedules. Include a basic understanding of what NOT to touch and who is recommended to touch it. A description of each major HVAC system, including designed capabilities, limitations, usage instructions, location, pictures as needed and acceptable performance for each major system, identifying key performance metrics / benchmarks and accountability / follow-up requirements. Sequence of operation (control) for each major HVAC system, including setpoints, schedules, energy efficiency features and seasonal changeover procedures. Identification of overall energy performance trends for each system if known and recommended techniques to aid in verifying performance or troubleshooting problems. An itemized list of all equipment to be maintained including known maintenance requirements, procedures or best practices. A list of any necessary training requirements or issues. A list of pertinent contact references. A log of events including dates and relevant issues and contact information: audits or surveys (maintenance, energy, lighting); purchases, replacement of equipment or new installations; building modifications; maintenance or testing; staff or contract changes; and problems identified and corrected. A questionnaire that guides new supervisors in acquiring relevant information from the departing supervisor. A copy of important as-built drawings. A copy of a recent HVAC load calculation and TAB reports. The current annual utilities usage report. Relevant information from any commissioning report and updates if completed; the problem log and correction plan, pertinent checks and tests, a list of improvements made and sensor calibration data. Reference to location of Equipment Manuals, Shop Drawings, O&M Manuals. National Center for Supercomputing Applications Site Contact Information Maintenance Division F&S Service Office 217.333.0340 http://my.fs.illinois.edu Tedra Tuttle Building Coordinator – National Center for Supercomputing Applications [email protected] 217.244.4480 Building Narrative 01 This section is dedicated to the ever evolving history of the building in general, including remodels, additions, building uses, etc… It is here to introduce a stranger and a friend to the building under care. Building Narrative 01 The National Center for Supercomputing Applications was founded in 1986 by the National Science Foundation. This “center” has always been located in Urbana/Champaign, but it wasn’t until 2003 that a building was built specifically for supercomputing. Prior to 2003, it occupied nine different buildings on the UIUC campus, and a single building in Virginia. The building was completed in 2005 and most researchers were able to move to this new building. Though many of the researchers utilizing the supercomputers at NCSA are affiliated with the University, scientists and engineers across the United States can access these machines remotely. The National Center for Supercomputing Applications has a gross square footage of 141,708 and is located on the north side of the campus, at 1205 W. Clark Street in Urbana. The current supercomputers at NCSA are Mercury (10 teraflops), Cobalt (8 teraflops), Abe (89 teraflops), and Lincoln (47 teraflops). The term teraflop is described as 1 trillion calculations per second. Currently, NCSA is working with IBM on a new system called Blue Waters, which is due to come online in 2011. Blue Waters will perform 1 quadrillion calculations every second (which will be known as a petaflop). The center focuses on helping all types of research by developing and exploring techniques to accelerate scientific computing. The center also works to help research communities fully exploit the extraordinary resources available on the internet with cyberenvironments. The following is a current timeline of the National Center for Supercomputing Applications building and its systems: o 2003: Building began construction. o 2005: Dedication of NCSA. o May, 2010: The building was visited by the Retrocommissioning Team, Division of Utilities and Energy Services with Facilities and Services of the University of Illinois. (Information cited above is credited to: http://www.ncsa.illinois.edu/ and other internet sites at the University of Illinois website featuring NCSA) Page 1 of 4 Wednesday, August 10, 2011 Building Narrative 01 PLUMBING SYSTEMS __________________ No investigation has been made of the plumbing systems as of the time of this narrative. HVAC SYSTEMS ____________________ The building is connected to the central campus chilled water loop and has a functioning chilled water meter presently. The steam meter resides in the basement mechanical room. There are two significant air handling units in the building totaling 136,000 CFM which run 24/7. There are three steam-to-water converters in located in the basement mechanical room. These are controlled per DDC. One serves the reheat system while the other two serve the perimeter radiation system. Each has a set of pumps. The entire building is controlled per Direct Digital Controls, right down to the wall thermostats and VAV boxes with reheat coils. The current system is Siemens Building Technologies. The HVAC system at the room level is controlled per occupancy sensor, when activated the box controls to the stat, but when unoccupied the box goes completely closed. The entire control system can be viewed online through Siemens web graphics or terminal server. ELECTRICAL SYSTEMS __________________ The electrical systems in the building appear to be original equipment but have not been reviewed thoroughly. OTHER SYSTEMS ____________________ No other systems were noted or investigated at the time of this writing. Page 2 of 4 Wednesday, August 10, 2011 Building Narrative 01 SITE PLOT PLAN ____________________ Figure 1: Site Plot Plan OCCUPANCY REQUIREMENTS & SCHEDULING __________ This building is used by graduate students and acclaimed faculty on a regular basis, remaining in the labs into the late hours of the night and early morning. There are hours of operation for the facility and the HVAC controls have been programmed to run according to those schedules. Such schedules apply to the perimeter offices, while the labs are constant volume. Any changes desired should be referred to Facilities and Services DDC Programmers. EMERGENCY RESPONSE __________________ This facility is not an emergency command center and is not currently used as a staging area. In case of an emergency refer to: http://www.dps.illinois.edu/emergencyplanning/emergency.response.html to locate telephone numbers and methods to safely encounter many emergency situations. Page 3 of 4 Wednesday, August 10, 2011 Building Narrative 01 INDOOR ENVIRONMENTAL QUALITY REQUIREMENTS ______ This facility requires optimum temperature control in each of the spaces where collections are stored. The desired occupied temperature should be kept between 70 deg F and 74 deg F depending on the season. A setpoint of 72 deg F is preferred to meet the thermal comfort for the majority of the visitors and employees. The desired relative humidity is 50% with a tolerance level of +/- 10%. The use of outdoor air is encouraged for adequate ventilation and “free” cooling, as long as the relative humidity levels are not compromised. UTILITY COST / ENERGY SAVING GOALS __________ The primary energy saving goals for this site are to limit energy use when the building is unoccupied, taking full advantage of reducing air flows in the offices during unoccupied hours. DOCUMENTATION AND TRAINING NEEDS __________ The building operations director, assistants, building mechanics, and any route mechanics who will adjust, troubleshoot, or work on the air handling units or their associated parts, MUST be trained in accessing the DDC control system information. They MUST be able to understand setpoints, schedules, and diagnosing minor system upsets using trend reports. If such mechanic does not understand the system, then a mechanic who does should be contacted for assistance and training. This system manual must be provided to staff for the successful daily operations and maintenance of the facility to preserve the facility in its best condition. Retrocommissioning can not and will not be held responsible for system degradation after the visiting period due to lack of follow through on the proper maintenance. PERFORMANCE ACCEPTANCE CRITERIA ____________ The primary criterion used to define acceptable performance for this facility is the requirement to limit occupant complaints while maintaining reasonable utility bills. The systems should rarely be forced out of service. Occupied space should be kept inside the 70F – 74F zone year round and “hot” and “cold” calls minimized. To provide this performance, the HVAC control system must function properly and be viewable through graphical information. The operators must be able to adjust setpoint temperatures and humidity levels. Page 4 of 4 Wednesday, August 10, 2011 Building Floor Plans & Schematics 02 This section is dedicated to floor plans identifying locations throughout the building. This can be useful for noting equipment, control panel locations, elevator numbering, fire extinguishers or other such essential items that require knowledge of the layout of the building. Owner’s Operating Requirements 03 This section is dedicated to the Building Facility Manager. It allows space for noting experiences, occupancy schedules, and specific conditions that the Owner wishes to achieve in the building. Owner’s Operating Requirements 03 Equipment Inventory and Description National Center for Supercomputing Applications Page 1 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Table of Contents Equipment Inventory and Description ........................................................................................ 1 OVERVIEW ...................................................................................................................................... 3 AIR HANDLING UNIT #1 (AHU1) ....................................................................................................... 4 AIR HANDLING UNIT #2 (AHU2) ....................................................................................................... 8 EXHAUST FAN #1 (EF1) ................................................................................................................. 11 EXHAUST FAN #2 (EF2) ................................................................................................................. 12 EXHAUST FAN #3 (EF3) ................................................................................................................. 13 CHILLED WATER SYSTEM ............................................................................................................... 14 REHEAT HOT WATER SYSTEM ........................................................................................................ 15 PERIMETER HOT WATER SYSTEM ................................................................................................... 17 Page 2 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 OVERVIEW The controls for this building appear to be in good shape. There is a programming issue with control of the perimeter heating system. The control valves for the humidifiers leak supply steam to the humidifiers when there is no call for humidification. Frank Boland Shop 41 Rep. Todd Nicholas Shop 55 Rep. Over-temperature protection was added to the hot water reheat converter (HX-1) and overtemperature protection was added to the glycol perimeter/preheat converters (HX-2, HX-3). This building seems to be working pretty well. There are a few things I would recommend to do here. The first thing I would do is to reprogram the perimeter heat valves to operate with the reheat valves as I seem to think that the reheat is satisfying the room temp before the perimeter valve gets a command to open. They both work off the same control loop which is 0 to 100%. The reheat valve works from 0 to 100% of the loop and the perimeter valve works from 50 to 100% of the loop. In most cases I believe the perimeter valve is never opening, and if your desk is next to the window it may be quite cold in the winter. The next thing I would do is replace the occupancy sensors in the rooms with the better occupancy sensor if the old ones go bad. They are a Leviton model OSW12-MOW which has motion detection as well as sound detection. I have replaced a few with this model, and they have worked very well. They still only have a 30 minute delay max like the other occupancy sensors. We have found bad occupancy sensors while changing out the power packs for them from an ODP20-070 to an OSP20-RDO. The reason for changing the power pack is the ODP20-070 doesn’t have an extra set of dry contacts for the HVAC control. So once we hook up the VAV box controllers to the occupancy sensors the box will keep going on and off intermittently because the occupancy sensor is out to lunch and someone has disconnected the light circuit from the power pack relay to keep them from going on and off. This should have been fixed when the lights weren’t working properly. Next, the humidifiers need to be fixed as well. I don’t think they have ever worked or the water they are using in it is very pure. The humidifiers look brand new. When we looked at them the tank temperatures were around 130 degrees and there wasn’t any water in the tanks. The reason there wasn’t any water in the tanks is that the fill had been disabled on the touch pad for the control of the humidifiers. The reason I think is that the two 2 inch steam valves that are supplying low pressure steam to them are leaking through all the time when the BAS isn’t calling for them to be open , thus putting steam into the AHU’s when you don’t want any humidification, especially in the summer time. Last but not least, I would entertain putting C02 sensors in the return air ducts of both air handlers as to limit the amount of outdoor air that is being introduced in to the mixed air plenum. Why bring it in if you don’t need it? I have been told this is not feasible, but I tend to disagree. Also maybe entertain installing temperature sensors after the preheat coil as to tell if you may have a blown diaphragm on the valve actuator or a leaking valve. Page 3 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 AIR HANDLING UNIT #1 (AHU1) Floor Plan Air Balance Schematic Control Diagrams Upon initial inspection of the unit I found that 5 of the 9 housing access doors had damaged door gaskets. I repaired the damaged door gaskets. Charles Jenkins Shop 6 Rep. While inspecting the dampers I found the Max Outside Air damper had a broken mounting bracket and on the control shaft coupler there was a missing roll pin. With these defects on this damper it was impossible for the damper to actuate. The motors would move but the damper would remain in the open position. I repaired the broken mounting bracket and a roll pin was reinstalled into the control shaft coupler. The damper now operates properly. An inspection of the remaining dampers revealed them to be in proper working order. The cooling coils appear clean and free of debris, and the drain pans are clean and are draining properly. While inspecting the humidifier section of the unit I found that there was some missing insulation on one of the cooling lines. The resulting condensation on this has dripped onto the floor of the housing and has started to rust the floor. The insulation needs to be repaired so no further damage is done to the floor of the housing. On 24 May 2010, 1:05 P.M. I took initial CFM readings across the heating coils with the dampers at: Min. O.A. @ 100% Max. O.A. @ 0% Exhaust damper @ 0% R.A. @ 100% I read an average of 644FPM. This translates to 51520 CFM. Page 4 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 The fan was running at 43.2 Hz and 82.3 Amps. Outside air CFM was calculated by temperature difference and was at approximately 19%, 9789 CFM. Frank Boland Shop 41 Rep. S1 Equipment Description Summary Air handling unit S1 contains a minimum outside air damper, an outside air damper, a set of mixed air dampers (a return air damper and a relief air damper), a glycol preheat coil, a humidifier, a chilled water coil a centrifugal supply fan, a centrifugal return fan, and static safety devices. Mixed Air Dampers Equipment Description Summary The mixed air dampers (relief air damper and the return air damper) have three Barber Colman actuators (one actuator on the relief air damper and two actuators on the return air dampers). The return air dampers receive a 4-14 psi signal from the Mixed Air transducer located in the control cabinet on the South side of AHU S1.The minimum outside air damper and the outside air damper receive a 4-14 psi signal from the Min. O.A. Damper transducer and the O.A. Damper transducer. The positioners for all damper actuators are set for 4-14 psi. Chilled Water Coil/Valve-Freeze stats Equipment Description Summary The normally closed chilled water valve (Siemens #599-05992) receives a 2.9 psi – 14.94 psi control signal from the CLG VALVE transducer. The positioner for this valve is set for 4-14 psi. Preheat Coil/Valve Equipment Description Summary The normally open glycol preheat control valve (Siemens #599-05961) receives a 2.9 psi – 14.95 psi control signal from the HTG VALVE transducer. The positioner for this valve is set for 4-14 psi. Steam Humidifier Equipment Description Summary The humidifier for S1 (equipment tag CSG 1) is a DriSteam STS 800C . The control valves serving the humidifier are normally closed 2” Siebe VK7283-613-4-11. There are two control valves per humidifier. These humidifiers do not have positioners. The spring range on the humidifier control valves is 6-1/2 psi to 12 psi. These valves receive a 6.01psi signal (at 4 volts) and an 11.61 psi signal at (7.98 volts) from the HUM VALVE transducer. The HUM SHUTOFF transducer outputs 6.6 psi – 9.65 psi to a P/E switch located in the humidifier control cabinet AHU Safety Devices Low Static Safety Mixed Air Static Suction Safety High Discharge Static Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c As found setting = -2.17 in. w.c. As left setting = -2.17 in. w.c Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c. As found setting = -2.1 in. w.c As left setting = -2.1 in. w.c. Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c As found setting = 3.7in. w.c. As left setting = 3.7 in. w.c. Page 5 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Equipment Data: Damper Actuators Minimum Outdoor Air Outdoor Air Relief Air Return Air Siemens 6” Actuator Prod. No. 322-3011 Positioners Minimum Outdoor Air Powers Controls Outdoor Air Positioning relay Relief Air Prod. No. 147-2000 Return Air Transducers Honeywell E/P Transducer CLG VALVE RP7517B016-1 HTG VALVE Input = 2-10 volts 0.1 ma MIXED DAMPER Output = 3-14.5 psi OA DAMPER MIN OA DAMPER HUM VALVE HUM SHUTOFF Static Safety Devices Low Static Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c Mixed Air Static Suction Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c. High Discharge Static Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c Pressure Transmitters Building Static Setra Model 264 Range +/- 1.0 in. w.c. p/n 2641001WB11T1C Duct Static Todd Nicholas Shop 55 Rep. Setra Model 264 Range 0 – 5 in. w.c. p/n 2641001WB11T1C This fan is located in the basement in room 01 on the west side of the room. The supply and return fans run via VFD’s of the Abb 800 type. The VFD minimum set points are 15 hertz. The supply fan and return fan VFD’s are getting speed references and start/stop commands from the BAS. Both VFD’s are sending back run status and VFD alarm status back to the BAS. Both the supply and return fans are plug type fans and are totally controlled by the BAS which is of the Siemens Appogee type control. There is one MEC controller that is node 20 that has 3 expansion point block controllers. All of the dampers and control valves are electric to pneumatic control via the Honeywell type transducers that control from 2-10 vdc to 3-15 psi. They consist of chilled water valve, heating valve, mix air dampers, outdoor air damper, min. outdoor air damper, humidity valve, and humidifier shutdown. We calibrated all of the transducers in software as the Honeywell transducers can’t be field calibrated. We replaced the mixed air dampers transducer on this unit. There are 2 humidity sensors on this unit, Discharge air humidity and return air humidity sensors. We found the discharge air humidity sensor to be bad and replaced it with a Vaisaila HMD 60U type sensor. The original sensor Page 6 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 was of the Siemens type 538-891 Duct RH-2-I. We calibrated all the analog pressure sensors that consisted of building static pressure, supply air duct static pressure, discharge static pressure, supply air pressure, mixed air static pressure, and return air pressure. We found that all of these sensors to be out of calibration at this time. We calibrated all the digital pressure safety switches that consisted of mix air static pressure, low static pressure, and high static pressure. We found all of theses devices to be working properly at this time. This fan has 3 temperature sensors that consist of supply air temp, return air temp, and mixed air temp. We calibrated all of theses sensors and found that they were a bit off calibration, but not bad enough to warrant a sensor replacement. Page 7 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 AIR HANDLING UNIT #2 (AHU2) Floor Plan Air Balance Schematic Control Diagrams While inspecting the dampers it was found that there was a leaking positioner on the Min Outside Air damper that effects the proper operation of this damper. Temperature Control is working to rectify the problem. Charles Jenkins Shop 6 Rep. An inspection of the remaining dampers revealed them to be in proper working order. The cooling coils appear clean and free of debris, and the drain pans are clean and are draining properly. While inspecting the humidifier section of the unit I found that there was a section of the floor that had begun to rust. I believe this is due to a seam on the housing floor that does not allow the standing water to reach the drain. This problem needs to be addressed to avoid further deterioration of the housing floor. On 6 June 2010, 1:05 P.M. I took initial CFM readings across the heating coils with the dampers at: Min. O.A. @ 100% Max. O.A. @ 0% Exhaust damper @ 0% R.A. @ 100% I read an average of 370 FPM. This translates to 29,600 CFM. The fan was running at 29.77 Hz and 54.5 Amps. Outside air CFM was calculated by temperature difference and was at approximately 10% or 2,960 CFM. Equipment Description Summary Air handling unit S2 contains a minimum outside air damper, an outside air damper, a set of mixed air dampers (a return air damper and a relief air damper), a glycol preheat coil, a humidifier, a chilled water coil a centrifugal supply fan, a centrifugal return fan, and static safety devices. Page 8 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Frank Boland Shop 41 Rep. Mixed Air Dampers Equipment Description Summary The mixed air dampers (relief air damper and the return air damper) have three Barber Colman actuators (one actuator on the relief air damper and two actuators on the return air dampers). The return air dampers receive a 4-14 psi signal from the Mixed Air transducer located in the control cabinet on the South side of AHU S2.The minimum outside air damper and the outside air damper receive a 4-14 psi signal from the Min. O.A. Damper transducer and the O.A. Damper transducer. The positioners for all damper actuators are set for 4-14 psi. Chilled Water Coil/Valve-Freezestats Equipment Description Summary The normally closed chilled water valve (Siemens #599-05992) receives a 2.9 psi – 14.94 psi control signal from the CLG VALVE transducer. The positioner for this valve is set for 4-14 psi. Preheat Coil/Valve Equipment Description Summary The normally open glycol preheat control valve (Siemens #599-05961) receives a 2.9 psi – 14.95 psi control signal from the HTG VALVE transducer. The positioner for this valve is set for 4-14 psi. Steam Humidifier Equipment Description Summary The humidifier for S2 (equipment tag CSG 2) is a DriSteam STS 800C . The control valves serving the humidifier are normally closed 2” Siebe VK7283-613-4-11. There are two control valves per humidifier. These humidifiers do not have positioners. The spring range on the humidifier control valves is 6-1/2 psi to 12 psi. These valves receive a 6.01psi signal (at 4 volts) and a 11.61 psi signal at (7.98 volts) from the HUM VALVE transducer. The HUM SHUTOFF transducer outputs 6.6 psi – 9.65 psi to a P/E switch located in the humidifier control cabinet AHU Safety Devices Low Static Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c As found setting = -2.17 in. w.c. As left setting = -2.17 in. w.c Mixed Air Static SuctionSafety Powers High Discharge Static Safety Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c. As found setting = -2.1 in. w.c As left setting = -2.1 in. w.c. Equipment Data: Damper Actuators Minimum Outdoor Air Outdoor Air Relief Air Return Air Positioners Minimum Outdoor Air Outdoor Air Prod. # 141-0575 1 in. w.c. to 12 in. w.c As found setting = 3.7in. w.c. As left setting = 3.7 in. w.c. Siemens 6” Actuator Prod. No. 322-3011 Powers Controls Positioning relay Page 9 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Relief Air Return Air Prod. No. 147-2000 Transducers Honeywell E/P Transducer CLG VALVE RP7517B016-1 HTG VALVE Input = 2-10 volts MIXED DAMPER Output = 3-14.5 psi OA DAMPER MIN OA DAMPER HUM VALVE HUM SHUTOFF Static Safety Devices Low Static Safety Mixed Air Static Suction Safety High Discharge Static Safety 0.1 ma Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c. Powers Prod. # 141-0575 1 in. w.c. to 12 in. w.c Pressure Transmitters Building Static Setra Duct Static Todd Nicholas Shop 55 Rep. Model 264 Range +/- 1.0 in. w.c. p/n 2641001WB11T1C Setra Model 264 Range 0 – 5 in. w.c. p/n 2641001WB11T1C This fan is located in the basement in room 01 on the west side of the room. The supply and return fans run via VFD’s of the Abb 800 type The VFD minimum set points are 15 hertz. The supply fan and return fan VFD’s are getting speed references and start/stop commands from the BAS. Both VFD’s are sending back run status and VFD alarm status back to the BAS. Both the supply and return fans are plug type fans and are totally controlled by the BAS which is of the Siemens Appogee type control. There is one MEC controller that is node 21 that has 3 expansion point block controllers. All of the dampers and control valves are electric to pneumatic control via the Honeywell type transducers that control from 2-10 vdc to 3-15 psi. They consist of chilled water valve, heating valve, mix air dampers, outdoor air damper, min. outdoor air damper, humidity valve, and humidifier shutdown. We calibrated all of the transducers in software as the Honeywell transducers can’t be field calibrated. We replaced the chilled water valve transducer on this unit. There are 2 humidity sensors on this unit, Discharge air humidity and return air humidity sensors. We found the discharge air humidity sensor to be bad and replaced it with a Vaisaila HMD 60U type sensor. The original sensor was of the Siemens type 538-891 Duct RH-2-I. We calibrated all the analog pressure sensors that consisted of building static pressure, supply air duct static pressure, discharge static pressure, supply air pressure, mixed air static pressure, and return air pressure. We found that all of these sensors to be out of calibration at this time. We calibrated all the digital pressure safety switches that consisted of mix air static pressure, low static pressure, and high static pressure. We found all of theses devices to be working properly at this time. This fan has 3 temperature sensors that consist of supply air temp, return air temp, and mixed air temp. We calibrated all of theses sensors and found that they were a bit off, but not bad enough to warrant a sensor replacement. Page 10 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 EXHAUST FAN #1 (EF1) Floor Plan Charles Jenkins Shop 6 Rep. Todd Nicholas Shop 55 Rep. Air Balance Schematic Control Diagrams This exhaust fan serves the rest rooms and break rooms. It is a mushroom style Greenheck fan. This fan operates in conjunction with unit AHU-1 the software code states that when AHU-1 is on, so is EF-1. Upon initial inspection (18 May 2010) of the fan I found that the belts were in disrepair and not turning the fan. The motor was running but the fan was not turning. I installed new belts (20 May 2010) and the fan is now running. On 6/9/2010 I traversed the duct work for this fan and found it to be exhausting 9360 CFM. This fan is located on the roof above room 4050D by going through door 4046 and going up the stairs through the roof access hatch. There is a 5hp 3phase motor on this fan that starts across line voltage via combination starter disconnect located at the bottom of the stairs in room 5001 which is an elevator equipment room. This starter is controlled by the BAS that will give the fan a start/stop command and receive run status from the starter. There is also an expansion block wired from MEC node 21 in this room next to the combination starter disconnect for the exhaust fan that the start/stop and the run status is wired to. The program calls for this exhaust fan to start and run whenever AHU-1 has a run status input to the controller. I didn’t find any problems with this fan other than maybe moving the combination starter disconnect for this fan into room 4046, and possibly moving the TT switch that is located on the fan on the roof to a better location for the persons who have to service this fan. Page 11 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 EXHAUST FAN #2 (EF2) Floor Plan Air Balance Schematic Control Diagrams (No picture available) This exhaust fan serves the IT lab, and is a six inch snorkel vent. At the time of inspection (19 May 2010) I was unable to get the fan to operate. The disconnect switch is located adjacent to the fan location in room 2003 with a hand/off/auto switch. Therefore I was unable to take readings to determine CFM’s. Charles Jenkins Shop 6 Rep. Todd Nicholas Shop 55 Rep. As Chuck said this fan serves a snorkel hood in room 2003 which is a computer IT room. This fan runs via a combination starter disconnect, with a hand/off/auto selector switch. This fan will not operate as there is a blown fuse on the 3 phase 480 volts feed into the disconnect, therefore not letting the control power transformer to work and not letting the starter contactor to pull in. I have been instructed to leave this fan starter as is. Page 12 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 EXHAUST FAN #3 (EF3) Floor Plan Charles Jenkins Shop 6 Rep. Todd Nicholas Shop 55 Rep. Air Balance Schematic Control Diagrams This exhaust fan serves the basement mechanical room. It is a Greenheck barrel style fan. It operates in conjunction with AHU-2; the software code states that when AHU-2 is on so is EF3. In the interest of saving energy, it may be possible change the way this fan is controlled and have it be controlled by a thermostat that would be located in the serviced area, therefore eliminating the need for this fan to run 24/7. I traversed the ductwork for this exhaust fan and found it to be exhausting 5404 CFM. This fan is located in the basement in room 01 hanging from the ceiling just west of AHU-2. This fan runs via a combination starter disconnect that is located on the north wall in the C2 hall way just south of the relief air areaway. This starter is controlled by the BAS that will give the fan a start/stop command and receive run status from the starter. This fans serves the mechanical equipment room and is programmed to start whenever there is an run status indication to the BAS controller. We may want to install a wall mount thermostat in this area so that the exhaust fan will only run when necessary. Page 13 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 CHILLED WATER SYSTEM Floor Plan Air Balance Schematic Control Diagrams (No picture available) Frank Boland Shop 41 Rep. Building Chilled Water System Equipment Description Summary Chilled water is supplied to the building thru the campus chilled water loop. Chilled water from the campus loop enters the building in the basement mechanical room B01 A normally open chilled water valve is located in the building chilled water supply piping and a normally open return valve is located in the building return piping. The chilled water entrance valve is controlled by pressure differential thru the ddc control system. The chilled water differential pressure sensor is located in the basement downstream of the chilled water entrance valve. Building Chilled Water Location: Differential Pressure Todd Nicholas Shop 55 Rep. Basement Mechanical Room B01 Setra Gage Pressure Transmitter Part # 2301050PD2F11B Range 0 -50 PSID Ecit: 24VDC Output: 4 – 20 ma This system is located in the basement in room 01 on the south east side at the ceiling elevation. The system consists of a flow control valve (supply side), an isolation valve (return side), an flow meter, and a pressure differential pressure sensor. The flow control valve is controlled via a electric to pneumatic transducer of the Honeywell type. The flow control valve is controlling to maintain a 30 psi pressure differential between the supply and return chilled water lines. The pressure differential sensor is located in the basement in close proximity to the chilled water entrance, so I think that is why the Set Point is so high. The chilled water system is maintaining a differential pressure of about 24 psid with the control valve 100% open. The flow meter is of the Rosemont anubar type and is reading between 200 and 300 GPM. I suspect that the differential pressure sensor may be out to lunch and needs to be calibrated and or replaced. We didn’t see any pressure drop across the strainer on the supply side so we are not sure why the system won’t maintain its DP set point at this time. I checked the open and closed limits on both the supply and return valves and they seemed to be operating correctly at this time. Page 14 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 REHEAT HOT WATER SYSTEM Floor Plan Frank Boland Shop 41 Rep. Air Balance Schematic Control Diagrams Hot Water Reheat System Equipment Description Summary The hot water reheat system is located in the Basement Mechanical Room 01. The hot water reheat system consists of a shell and tube convertor, a normally closed Cashco control valve, and two hot water pumps, P-1 and P-2.. The automatic fill for the hot water reheat system is located on the North wall near the perimeter reheat pumps. Start/Stop control and pump rotation of P-1 and P-2 is provided by the DDC control system. An immersion temperature probe in the hot water supply piping at the convertor provides control of the steam control valve. VFD pump spee d is controlled by a Setra differential pressure transmitter. This DP transmitter is located immediately North of Room 3102C above the ceiling. An Johnson Controls aquastat has been installed on the convertor supply piping to provide high limit temperature protection of the reheat hot water supply. An e/p located in the control cabinet will bleed the control signal in the event of Reheat Water Transducers REHEAT Honeywell E/P Transducer RP7517B016-1 Input = 2-10 volts 0.1 ma Output = 3-14.5 psi SPARE FOR Honeywell E/P Transducer REHEAT RP7517B016-1 Input = 2-10 volts 0.1 ma Output = 3-14.5 psi NOTE: At one time the reheat exchanger was controlled by a 1/3 and 2/3 control valve arrangement. This valve arrangement has been changed to a normally closed Cashco ball valve. This change has freed up the 2/3 transducer; this transducer was calibrated and labeled as SPARE FOR REHEAT EXCHANGER. Page 15 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Todd Nicholas Shop 55 Rep. There is one heat exchanger (HE-1) with two hot water pumps on the system that run via VFD’s of the ABB 800 type. The heat exchanger steam valves and pumps are totally controlled by the BAS of the Siemens Appogee type control. There is one MEC controller that is node 22 with 3 expansion point modules. The BAS is giving the VFD’s for pumps P1 and P2 start/stop commands and speed references. The VFD’s are giving the BAS run status and alarm status inputs to the controller. The heat exchanger has a hot water supply temp sensor and a hot water return temp sensor wired back to the BAS controller. The 2 hot water pumps are redundant as only one pump should be running at any given time. If the lead pump should shut off for any reason the lag pump will get a command to start and run to maintain a differential pressure of 8.5 psid. The differential pressure sensor is located on the 3rd floor above the ceiling outside of room 3102C. This sensor is of the Setra type and it is a 0-50 psid, 4 – 20 ma device. We calibrated this device and found it to be out of calibration and it was set up wrong in software. It was set up in software as a 0 - 60 psid device not a 0 – 50 psid device. We corrected this problem as well, and the sensor is reading correctly at this time. The BAS is also controlling two steam valves for the heat exchanger. A 1/3 and a 2/3 type steam valves that are N.O type valves. They are electric to pneumatic controlled valves via 2 transducers of the Honeywell type that put out 3 –15 psi via 2-10 volts DC from the BAS controller analog outputs. We calibrated both transducers and found that they were working correctly. One steam valve has been taken out and only the 1/3 valve transducer is in operation at this time. Not sure why that is, but it seems to be working with a outdoor air temp of 70-90 degrees and a 120 degree hot water supply set point. We calibrated both the hot water supply temp and the hot water return temp sensors and found that they were a little off but working ok at this time. Page 16 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 PERIMETER HOT WATER SYSTEM Floor Plan Frank Boland Shop 41 Rep. Air Balance Schematic Control Diagrams Perimeter Heating System Equipment Description Summary The perimeter heating system is located in the Basement Mechanical Room 01. The perimeter heating system consists of two shell and tube convertors (Heat Exchanger 1 and Heat Exchanger 2), a normally open 1/3 control valve and a normally open 2/3 control valve for each convertor, and two hot water pumps, P-3 and P-4. The automatic fill for the perimeter heating system is located on the North wall near the perimeter reheat pumps. The perimeter heating system is a glycol system; the perimeter heating system also serves the preheat coils on S1 and S2. Start/Stop control and pump rotation of P-1 and P-2 is provided by the ddc control system. An immersion temperature probe in the hot water supply piping at the convertor provides control of the steam control valves. VFD pump speed is controlled by a Setra differential pressure transmitter. This DP transmitter is located above the ceiling in Room 3102C. An Johnson Controls aquastat has been installed on the convertor supply piping to provide high limit temperature protection of the perimeter water supply. An e/p located in the control cabinet will supply main air to the control valves in the event of high temperature. Perimeter Transducers HE1 1/3 Honeywell E/P Transducer HE1 2/3 RP7517B016-1 HE2 1/3 Input = 2-10 volts 0.1 ma HE2 2/3 Output = 3-14.5 psi Todd Nicholas There are two heat exchangers (HE-2 and HE-3) with two hot water pumps on the system that run via VFD’s of the ABB 800 type. The heat exchangers steam valves and pumps are totally controlled by the BAS of the Siemens Appogee type control. There is one MEC controller that is node 22 with 3 expansion point modules. The BAS is giving the VFD’s for pumps P3 and P4 start/stop commands and speed references. The VFD’s are giving the BAS run status and alarm status inputs to the controller. The heat exchangers have a hot water Page 17 of 18 Thursday, August 11, 2011 Owner’s Operating Requirements 03 Shop 55 Rep. supply temp sensor and a hot water return temp sensor wired back to the BAS controller. The 2 hot water pumps are redundant as only one pump should be running at any given time. If the lead pump should shut off for any reason the lag pump will get a command to start and run to maintain a differential pressure of 14 psid. The differential pressure sensor is located on the 3rd floor above the ceiling inside of room 3102C. This sensor is of the Setra type and it is a 0-50 psid, 4 – 20 ma device. We calibrated this device and found it to be out of calibration and it was set up wrong in software. It was set up in software as a 0 - 60 psid device not a 0 – 50 psid device. We corrected this problem as well, and the sensor is reading correctly at this time. The BAS is also controlling two steam valves for the heat exchangers. A 1/3 and a 2/3 type steam valves that are N.O type valves. They are electric to pneumatic controlled valves via 2 transducers of the Honeywell type that put out 3 –15 psi via 2-10 volts DC from the BAS controller analog outputs. We calibrated both transducers and found that they were out of range and replaced them both and recalibrated. We calibrated both the hot water supply temp and the hot water return temp sensors on both heat exchangers and found that they were a little off but working ok at this time. Page 18 of 18 Thursday, August 11, 2011 Retrocommissioning Final Report 04 This section is dedicated to the Retrocommissioning Projects that have taken place during the life of this building. It holds the findings, recommendations and links to improving even further the quality of life for the residents and for the building systems. The Retrocommissioning website can be viewed at the following address: www.fs.illinois.edu/retro Retrocommissioning Final Report 04 National Center for Supercomputing Applications COMPLETION JUNE 2010 A work completed by This document is property of Facilities and Services, Retrocommissioning Team and is not to be revised, copied or distributed without the explicit consent of the Manager of the Team. This document is not intended to be dynamic, but rather a static report taken at one spot in time in order to compare with the past and with the future. © 2008 This document is based upon © 2005, Portland Energy Conservation Inc. (PECI). All rights reserved. Retrocommissioning Final Report 04 Table of Contents E x e c u t i v e S u m m a r y ........................................................................................ 3 P u r p o s e .............................................................................................................. 4 M e t h o d o l o g y ..................................................................................................... 4 D o c u m e n t a t i o n R e v i e w ............................................................................... 5 S i t e A s s e s s m e n t ........................................................................................... 5 A n a l y s i s o f D a t a ................................................................................................ 5 V e r i f i c a t i o n o f S a v i n g s ..................................................................................... 6 T h e P a t h t o S u c c e s s – M a i n t e n a n c e o f S a v i n g s ........................................... 6 Page 2 of 6 Monday, August 01, 2011 Retrocommissioning Final Report 04 Executive Summary The Retrocommissioning Team in conjunction with Facilities and Services Utilities and Energy Services Division completed retrocommissioning of this building for the University of Illinois. The work was funded by student fees in harmony with their vision to create a sustainable campus. Retrocommissioning, or returning a building to its originally intended design while integrating energy saving measures, is a snapshot in the life of a building that applies a systematic investigation process to improve and optimize a building’s operation and to offer suggestions to improve the overall maintenance. It is an independent process that focuses on the building’s energy using equipment such as the HVAC and other mechanical equipment, lighting equipment, and related controls. It may or may not emphasize bringing the building back to its original intended design specifications. In fact, via the process, the retrocommissioning team may find that the original specifications no longer apply. The process may result in recommendations for capital improvements, but its primary focus is to optimize the building systems via performing long-needed maintenance and care for aged systems, improving control strategies and allowing graphic displays, tailoring the building’s energy needs by its current tenants, and by improving the very nature of operations and maintenance. Details of this structured method are provided later in the report. The retrocommissioning process began in May of 2010. It involves a coordinated effort between the RCx Team, Directors of Utility & Energy Services and Maintenance, DDC Shop, Sheet Metal Shop, Temperature Controls Shop, DDC Programmers and the willing building staff. The process included reviewing documents, conducting informal interviews with staff and inhabitants of the spaces, performing field investigations, monitoring and analyzing building systems, developing a master energy conservation measures list, and assisting with selecting measures for implementation. Some of these findings were a mix of “operation and maintenance” repairs that had estimated paybacks of three years or less and “energy conservation projects” that were more costly to implement and therefore longer paybacks. Additional measures sprinkled in were improvements that had potential energy reduction and equipment maintenance impacts, but the reduction estimates were based more on experience rather than energy modeling or engineering estimates. A two-page current summary exists on the web at: www.fs.illinois.edu/retro/rcxcompprojects.htm Such implementation is ongoing and these preliminary results are rewarding. This report details the process taken to achieve these outstanding results and the encouragement to maintain these results. Page 3 of 6 Monday, August 01, 2011 Retrocommissioning Final Report 04 Purpose The University of Illinois has educated thousands of students over a period of a century. Many of the existing buildings on campus were designed and constructed during an era of abundance, when energy was abundant and economical. Buildings were designed around a certain space intent, which over the years has dramatically changed with new departments and space shifting. Operations and maintenance funding has not grown in proportion with the expansion of the real estate of the university. Maintenance folks have been stretched thin, assigned to care for 10, 15 or more buildings. Therefore, existing heating, ventilating and air conditioning equipment and associated equipment have been neglected. These factors have compounded to reduce the efficiencies and operation strategies of the hundreds of pieces of equipment throughout campus, requiring increased expenditures on energy utility costs and decreased tenant comfort. The future is showing an ever increasing utility market, and therefore the essential need for improving the way energy is used. For this very reason, the Retrocommissioning Project was funded to assist the University to reduce the maintenance items, lower energy consumption, educate building tenants, and give direction in using energy in a sustainable way. Methodology What is retrocommissioning? At the University of Illinois it a concentrated focus on the building’s HVAC systems, since they consume the majority of the energy in a building. It is a process whereby a team of engineers and technical individuals approach an existing building with the goal of saving energy and improving tenant comfort, while restoring the building systems to optimal performance. The process requires a review of the operations and maintenance currently conducted in the facility. During field investigations the team meets weekly and brainstorms on methods to improve the building’s performance and efficiency. The basic process requires five fundamental procedures: o o o o o Investigation and data collection Analysis of data Implementation of solutions Projects hand-off Verification of savings These steps take place concurrently. However, below the report shows in detail how the investigation and data collection takes place. The remaining pieces are placed in a table together to logically show the process at each point in time. The last part will discuss the verification of savings that resulted from the decisions made by the Retrocommissioning Team. Page 4 of 6 Monday, August 01, 2011 Retrocommissioning Final Report 04 Investigation and Data Collection The retrocommissioning process began by collecting and evaluating data pertaining to facility equipment and current operation. The primary tasks for this project are outlined below. Documentation Review The first step of the investigative process consisted of obtaining the latest existing air balance reports for the HVAC systems, gathering the temperature control drawings from the shops and 3rd party installations, as well as the HVAC floor plans for quantities and sizes of HVAC units. Shop drawings and energy data were also gathered and reviewed by the RCx Team. Site Assessment The next step was to conduct the site assessment. Questions were asked to ascertain the facility’s operating condition. Where specific known challenges were, what maintenance has been performed, and so on. Many weeks were spent in the building investigating each piece of HVAC equipment and its role in using energy. Each of its components was reviewed including: ductwork, coils, control sequences, the state of the control valves and pneumatic hardware. Occupancy schedules were noted, space temperatures were trended, and tenants were interviewed. Discussions took place with the route mechanics to gain a more in-depth understanding of the building HVAC equipment conditions over the last couple of years. Analysis of Data At each step along the way the findings were noted, then discussed at the weekly progress meetings. Decisions were made at many of these meetings and the actions were followed through on with the varying parties, which was sometimes immediate. Therefore, the list below is generated in the form of tables showing the 1) finding, 2) Proposed RCx Solution, 3) The implicated cost estimate and payback expected, 4) If the implementation took place or not, 5) Which party is/was responsible for actions. The implementation of solutions was dependent upon the costs and responsibility factors associated with such deficiencies. In many cases the RCx Team went ahead and resolved the findings with direction from Mr. Kent Reifsteck, Director of Utilities and Energy Services. These immediate adjustments helped facilitate the energy savings that are observed currently. Some solutions are quick paybacks, others of longer duration, and yet others that are based on qualified engineering principles and experience. Page 5 of 6 Monday, August 01, 2011 Retrocommissioning Final Report 04 Verification of Savings The data shows that the solutions implemented have had serious impacts on the amount of energy consumed and a payback of thousands of dollars. Data was collected over the last year in energy usage and has been compared to this year after the RCx Team visited. Charts of the energy reduction are frequently updated at the Retrocommissioning website at www.fs.illinois.edu/retro under “Projects” and then “Completed Projects”. The Path to Success – Maintenance of Savings A brand new vehicle that leaves the factory is perfect in every way; it’s been tested, proven, crashed, and trashed. When the proud new owner drives away, there is an air of confidence that the pieces will work in harmony and deliver the satisfaction they expect. However, this satisfaction will only continue as long as the Owner is responsible and learns to maintain its parts. Proud automobile ownership comes from a commitment to keep the auto in shape and tuned per the manufacturer’s instructions. Retrocommissioning has a very similar path. A brand new building, although having its quirks, still possess’ new equipment, new parts, and new warranties. However, the following year the equipment in the building needs care and preventative maintenance. Sometimes years or decades go by before a building is approached with the idea of restoring, or even improving upon, its efficiency. Retrocommissioning puts the building back on the path to success. After the Team leaves, the building is once again under the jurisdiction of the Facility Operators, Route Mechanics and Campus Administration. They bear the responsibility of continuing on the legacy of maintaining the building system in its best condition possible, operating at its peak efficiency, or better. To maintain the building at its peak efficiency, it will require help from “mechanics”, specifically trained route mechanics who know the building and its method of operation. It will require following up on preventative maintenance tasks or creating new ones to take care of repetitive causes contributing to system inefficiencies. This may require additional funds, but much less than the inefficiencies will. Control systems will need to be calibrated and checked. Utility data will be trended, kept monthly for seasonal comparisons, to review and alert the operator to any deviations. The operator will then need to understand what to do to maintain the energy savings and if not, to be able to speak with someone who can assist. F&S prides itself in offering this service to the campus. The Facility Operator and assistants are in the position to improve upon, or optimize the work performed by the Retrocommissioning Team. There are many other opportunities for savings. That event was a turning point. The operators should consider implementing steps outlined in the publication LEED for Existing Buildings which is available online at www.usgbc.org. Since there are many other buildings on campus to attend to, it may well be the only visit during this decade. Therefore, operator, assistants, and route mechanics: take your stewardship seriously! Treat the building and its systems as a brand new automobile. Commitment will lead the building and its caretakers on the Path to Success. Page 6 of 6 Monday, August 01, 2011 National Center for Supercomputing Applications #564 Building Gross Sq.Ft.: 141,708 Expected Simple Payback: 1.0 YR Retrocommissioning Team Visit Period: FY 2010 May-Jun Expected Annual Utility Avoidance: 32% OR ▼ 10,802 MMBTU Campus Energy Rank FY09: 38 Principal Building Use: Offices and Classrooms Facility Contacts: Tedra Tuttle & Trish Barker Building & Occupant Overview The National Center for Supercomputing Applications unites researchers with supercomputing needs or experiments on the Champaign-Urbana campus. The building was originally built in 2005. The building is home to multiple supercomputers that are capable of teraflop calculations. Various clubs and school events encouraging mathematical and technical advancement are welcomed at the facility. There are two VAV air handling units that condition the entire four story building along with dedicated computer room units (CRUs). The building’s cooling needs are met by the campus chilled water loop, while the heat in the building is provided by a combination campus steam and hydronic system. Building controls are Siemens MECs. Facility total metered energy during FY09 was 33,757 MMBTU. Post RCx Energy Use Intensity (EUI) & Cost Index (ECI) E.U.I. E.C.I. #1 E.C.I. #2* 162.0 kBTU / Sq.Ft. $3.28 / Sq.Ft. $2,110 / person Image .by evl.uic.edu Project Highlights • 300+ existing occupancy sensors were connected to the HVAC system to control 239 rooms only when occupied • Extensive PPCL code was written to allow for night setback of space conditioning • Exhaust fan serving the building restrooms was repaired and scheduled to maintain conditions when occupied • Existing chilled water meter found accurate at maximum flow but not so at lower flows. Meter was replaced for optimum results. • A bypass around the chilled water meter was installed to allow for uninterrupted cooling to the supercomputer rooms * 220 PEOPLE OCCUPY BUILDING AT ONE TIME. Retrocommissioning Specifics & Results The air handling units (AHUs) providing air conditioning were maintaining space conditions 24/7/365, with a setback sequence in place. The primary energy conservation method was connecting the existing occupancy sensors to the VAV box to condition the space only when occupied. Since 90% or better have a 8am to 5pm schedule, large quantities of energy use was avoided. Independent CRUs were monitored to guarantee satisfactory data cluster temperatures. To maintain comfort conditions, the VAV / perimeter heat sequence was reviewed. The radiation was not operating unless the reheat could not satisfy the space. This led to drafty offices. The sequence was rewritten to allow the perimeter radiation to operate independently of the reheat valve, thereby allowing the space to warm even if the VAV box was closed. Unoccupied setbacks were limited to a 10 degree deadband centered on the room setpoint. © University of Illinois, Urbana-Champaign, IL January 20, 2011 1 National Center for Supercomputing Applications #564 © University of Illinois, Urbana-Champaign, IL January 20, 2011 2 HVAC 05 This section is dedicated to the heating, ventilating and air conditioning tradesmen and associated engineers. It is here for any data related to the functioning, replacement, and energy consumption by the HVAC systems in the building. National Center for Supercomputing Applications - #564 Tag AHU-1 AHU-2 RF-1 RF-2 EF-1 EF-2 EF-3 CRU-07 CRU-1005 CRU-1045 CRU-2045 CRU-2105 CRU-3003A CRU-3003B CRU-3045 CRU-4045 CRU-5001 CRU-5101 LCM SA SA RA RA 125 125 60 60 Previous TAB Report (10/4/2005) 78,020 75,940 -66,177 -67,810 EA EA EA SA SA SA SA SA SA SA SA SA SA SA 7.50 1.50 3 0.5 3 0.5 0.5 3 7.5 7.5 0.5 0.5 0.2 0.5 -8,928 -529 -5,290 1,244 5,910 1,236 1,187 5,776 11,678 11,802 1,222 1,210 639 1,088 Area Served Entire west portion of building Entire east portion of building Entire west portion of building Entire east portion of building Air Balance This Unit General Exhaust Room 2003 General Exhaust RM. 07 RM. 1005 RM. 1045 RM. 2045 RM. 2105 RM. 3003 RM. 3003 RM. 3045 RM. 4045 RM. 5001 RM. 5101 HP VFD Actual CFM Design CFM Notes 75,000 75,000 -65,985 -70,055 BASEMENT 01 BASEMENT 01 BASEMENT 01 BASEMENT 01 8,990 550 4,970 1,200 5,675 1,200 1,200 5,675 12,000 12,000 1,200 1,200 700 1,200 ON ROOF 2ND FLOOR, ROOM 2003 BASEMENT 01 LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES LOCATED IN ROOM IT SERVES 0 Page 1 of 1 AIR HANDLING UNIT TEST REPORT Project: National Center for Supercomputing Applica System Unit: AHU-1 Date: 5/20/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins AHU Data Manufacturer Model Number Serial Number Total Cooling CFM Total Heating CFM Outdoor Air CFM Return Air CFM Arrangement No. of Pre-Filters Filter Sizes (in.) Filter Types No. of Bag Filters Bag Filter Sizes (in.) Bag Filter Type Design Air Flow Equipment Not Available 9,015 65,785 Draw Thru 45 5 24x24x4 12x24x4 Pleated Pleated 45 5 Final AIR FLOW EQUIPMENT NA NA 51,520 51,520 9,789 42,298 Draw Thru 5 45 24x24x4 12x24x4 Pleated Pleated 45 5 24x24x22 12x24x22 24x24x22 12x24x22 Design 75,000 Test Data Maximum Supply CFM Discharge S.P. (in.) Suction S.P. (in.) Total Δ S.P. (in.) BEFORE Return Fan Δ S.P. Blender Δ S.P. Filter Δ S.P. Preheat Coil Δ S.P. Cooling Coil Δ S.P. Supply Fan Δ S.P. Reheat Coil Δ S.P. CLASS 1 Not Available AFTER Final 51,520 1.93 -0.966 2.89 Preliminary 78,020 Δ BEFORE AFTER Δ BEFORE AFTER Δ 2.2 N/A N/A 0.26 0.86 6.4 N/A N/A -1.06 -1.4 -1.7 -2.54 N/A N/A -1.4 -1.7 -2.54 2.14 2.13 N/A 0.34 0.3 0.84 4.68 -0.43 -0.25 -0.26 -0.57 -0.67 -0.97 NA -0.01 -0.26 -0.57 -0.67 -0.97 1.93 NA 0.42 -0.01 -0.31 -0.1 -0.3 2.9 #VALUE! Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. The outside air volume was calculated by using temperature difference. There was approximately 19% outside air with the minimum outside air damper open 100% and the maximum outside air damper closed. The return air TAB 2-03 Page 1 of 3 SUPPLY FAN TEST REPORT National Center for Supercomputing Application System Unit: AHU-1 Project: Date: 5/20/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Design Air Flow Equipment N/A 125 460 3 60 0 CL ► CL Design 75,000 1,038 N/A 6.4 460 Final TWIN CITY FAN & BLOWER SIZE 551 04-189123-1-2 3 SIEMENS 444T 444-T 125 125 1,785 NOT READ 460 3 60 60 460 3 N/A N/A 1.15 143 BROWNING 5V5B110 5B5V110 3 3/8" 3-3/8 5 GOODYEAR 5VX1700 5VX1700 62" CL ► CL 61 5/8, +2 1/2-5 CL ► CL Preliminary Preliminary 78,020 1,043 N/A -2.54 2.14 4.68 131.3 129.7 130.2 460 82.3 Final 51,520 725 43.2 Hz 1.93 -0.966 2.89 82.3 460 82.4 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 5B5V184., Shaft Size: 3 7/16. The sheave on the motor is worn and needs replaced, also the sheave on the fan is worn and needs replaced. The isolation springs for the fan appear in good condition. The flex TAB 2-03 Page 2 of 3 RETURN FAN TEST REPORT National Center for Supercomputing Application System Unit: AHU-1 Project: Date: 5/20/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Design Air Flow Equipment N/A 60 460 3 60 0 CL ► CL Final TWIN CITY FAN & BLOWER SIZE 631 04-189123-2-1 3 SIEMENS 364-T 60 NOT READ 1,775 3 60 460 60 3 460 1.15 71 81.7 71 BROWNING 5B5V64 5B5V64 2 3/8" 2 3/8 5 5 GOODYEAR 5VX1700 5VX1700 63" CL ► CL 65 1/8,+2 1/2-3 CL ► CL Preliminary Design 65,785 579 N/A Preliminary 66,177 618 N/A 2.2 55.1 460 2.13 53.7 460 56.3 24.7 Final 42,298 395 31 Hz -0.43 -0.01 0.44 24.7 460 25 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 18 1/2 Dia., Shaft Size: 3 15/16. I was unable to locate the identifing numbers for the fan sheave. The sheave on the motor is worn and needs replaced. The isolation springs for the fan appear in good condition. TAB 2-03 Page 3 of 3 AIR HANDLING UNIT TEST REPORT Project: National Center for Supercomputing Applica System Unit: AHU-2 Date: 6/3/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins AHU Data Manufacturer Model Number Serial Number Total Cooling CFM Total Heating CFM Outdoor Air CFM Return Air CFM Arrangement No. of Pre-Filters Filter Sizes (in.) Filter Types No. of Bag Filters Bag Filter Sizes (in.) Bag Filter Type Design Air Flow Equipment Not Available 4,945 70,055 Draw Thru 45 5 24x24x4 12x24x4 Pleated Pleated 45 5 Final AIR FLOW EQUIPMENT NA NA 29,600 29,600 2,960 30,103 Draw Thru 45 5 24x24x4 12x24x4 PLEATED 45/5 24x24x22 12x24x22 24x24x22 12x24x22 Not Available Test Data Maximum Supply CFM Discharge S.P. (in.) Suction S.P. (in.) Total Δ S.P. (in.) Design 75,000 BEFORE Return Fan Δ S.P. Blender Δ S.P. Filter Δ S.P. Preheat Coil Δ S.P. Cooling Coil Δ S.P. Supply Fan Δ S.P. Reheat Coil Δ S.P. CLASS 1 BAG FILTERS AFTER Final 29,600 1.47 -0.38 1.85 Preliminary 75,940 Δ BEFORE AFTER Δ BEFORE AFTER Δ 3.25 N/A N/A 0.26 0.86 6.4 N/A N/A -1.09 -1.39 -1.67 -2.51 N/A N/A -1.39 -1.67 -2.51 2.17 2.51 N/A 0.3 0.28 0.84 4.68 -0.3 -0.03 -0.03 -0.22 -0.27 -0.38 NA 0.08 -0.03 -0.22 -0.27 -0.38 1.47 NA 0.38 0 -0.19 -0.05 -0.11 1.85 #VALUE! Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. The outdoor air CFM was calculated using temperature difference on 6/4/10. The volume of outdoor air with the unit at 100% return and the minimum outside air damper at 100% was approximatly 10%. The return air TAB 2-03 Page 1 of 3 SUPPLY FAN TEST REPORT Project: National Center for Supercomputing Applicatio System Unit: AHU-2 Location: 1205 West Clark Street, Urbana, IL Date: 6/3/2010 Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Design Air Flow Equipment N/A Preliminary 125 460 3 60 460 N/A 0 444T 125 1,785 3 60 N/A 5V5B110 3 3/8" 5VX1700 62" CL ► CL CL ► CL Design 75,000 1,038 N/A 6.4 460 Preliminary 75,940 1,055 N/A -2.51 2.17 4.68 128.7 130.1 129.3 460 Final TWIN CITY BLOWER SIZE 551 04-189123-1-1 3 SIEMENS 444-T 125 NOT READ 60 460 3 164.45 143 BROWNING 5B5V110 3 3/8 5 GOODYEAR 5VX1700 62 1/4,+2-4 CL ► CL 54.5 Final 29,600 521 29.77 -0.38 1.47 1.85 54.6 460 54.5 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 5B5V184, Shaft: 3 7/16, both the motor and fan sheaves are worn and need replaced. The belt guard for this fan has a broken mounting bracket and needs to be fixed before it can be reinstalled. The isolation TAB 2-03 Page 2 of 3 RETURN FAN TEST REPORT National Center for Supercomputing Applicatio System Unit: AHU-2 Project: Location: 1205 West Clark Street, Urbana, IL Date: 6/3/2010 Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Preliminary Design Air Flow Equipment N/A 60 460 3 60 0 460 71 3 60 81.7 5B5V70 2 3/8" 5 5VX1700 CL ► CL 62" CL ► CL Design 70,055 649 N/A Final TWIN CITY BLOWER SIZE 631 04-189123-2-2 3 SIEMENS 364-T 60 NOT READ 460 3 60 71 81.65 BROWNING 5B5V64 2 3/8 5 GOODYEAR 5VX1700 65 1/2,+2-3 CL ► CL Preliminary 67,810 642 N/A 3.25 53.1 460 2.51 53 460 54.3 24.75 Final 30,103 285 28.17 -0.3 0.08 0.38 24.76 460 24.75 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 18 1/2" dia. Shaft: 3 15/16, I was unable to locate any identifing marks on the fan sheave. The motor sheave is worn and needs replaced. The belt guard for this fan has a broken mounting bracket that needs TAB 2-03 Page 3 of 3 EXHAUST FAN TEST REPORT Project: National Center for Supercomputing Application System Unit: EF-1 Date: 6/9/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Preliminary Design GreenHeck GB-300-50-X 04F14422 5 460 3 60 460 6.7 3 60 7.7 2AK94 1 1/8" 2 AP42 11" CL ► CL Design 8,990 752 N/A CL ► CL Final GREENHECK GB-300-50-X 04F14422 NA TOSHIBA 184-T 5 1758 60 460 3 6.7 7.705 BROWNING 2VP50 1 1/8 2 GATES AX42 11, +1-1 CL ► CL Preliminary 8,928 802 N/A 1.5 5.8 460 1.41 5.9 460 5.8 6 Final 9,360 1033 NO VFD -0.68 NA #VALUE! 6.1 460 6.1 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 2AK94, Shaft: 1", The belts on this fan were found in disrepair, and not turning the fan (new belts have been installed). The fan and motor speed are actual speeds that were taken with a tachometer. The CFM for TAB 2-03 Page 1 of 2 EXHAUST DUCT TRAVERSE REPORT National Center for Supercomputing Applica SYSTEM UNIT: Project: DATE: 6/9/2010 Loc./Zone: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins AIR DENSITY: 0.0745 ALTITUDE: Air Temp. in Duct: ºF 800 Multiple Duct Calc. ROUND DUCT #1: ROUND DUCT #2: ROUND DUCT #3: ROUND DUCT #4: ROUND DUCT #5: CFM DUCT #1: CFM DUCT #2: CFM DUCT #3: CFM DUCT #4: CFM DUCT #5: FPM DUCT #1: FPM DUCT #2: FPM DUCT #3: FPM DUCT #4: FPM DUCT #5: Total CFM Multiple Duct Calc. RECT. DIM. DUCT #1: RECT. DIM. DUCT #2: RECT. DIM. DUCT #3: RECT. DIM. DUCT #4: RECT. DIM. DUCT #5: CFM DUCT #1: CFM DUCT #2: CFM DUCT #3: CFM DUCT #4: CFM DUCT #5: FPM DUCT #1: FPM DUCT #2: FPM DUCT #3: FPM DUCT #4: FPM DUCT #5: Total CFM Grand Total CFM Design IN. IN. IN. IN. IN. Design "W X "W X "W X "W X "W X DIA. DIA. DIA. DIA. DIA. "H "H "H "H "H EF-1 LB/CU.FT. FT. ↑ SEA LEVEL Preliminary IN. DIA. IN. DIA. IN. DIA. IN. DIA. IN. DIA. Preliminary "W X "W X "W X "W X "W X "H "H "H "H "H Final IN. IN. IN. IN. IN. 48 Final "W X 20 "W X "W X "W X "W X 9,360 DIA. DIA. DIA. DIA. DIA. "H "H "H "H "H 1,404 9,360 9,360 Remarks TAB 2-03 Page 2 of 2 EXHAUST FAN TEST REPORT National Center for Supercomputing Application System Unit: EF-2 Project: Location: 1205 West Clark Street, Urbana, IL Date: 5/20/2010 Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Preliminary Design Plymovent 1300 1/2 Horse 460 3 60 3 460 1 60 1.2 DD DD DD DD CL ► CL CL ► CL DD Preliminary 529 3,450 N/A Design 550 3,440 N/A 3.5 0.8 460 3 0.8 460 Final PLYMO-VENT 1300 N/A N/A LESSON C56C 1/2 HORSE 2850 460 60 3 1/1.3 #VALUE! DIRECT DRIVE N/A N/A N/A N/A N/A N/A CL ► CL Final 0.9 460 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. This exhaust fan is located in room 2003. It is a direct drive fan. There is only one 6" round snorkel vent connected to this fan, and it is controlled by a disconnet switch that is located on the wall adjacent to the snorkel TAB 2-03 Page 1 of 1 EXHAUST FAN TEST REPORT National Center for Supercomputing Application System Unit: EF-3 Project: Date: 6/9/2010 Location: 1205 West Clark Street, Urbana, IL Readings Taken By: Charles Jenkins Fan Data Manufacturer Model Number Serial Number Class Motor Make Motor Frame Motor HP Motor RPM Volts / Phase / Hz F.L. Amps / S.F. Motor Sheave Make Motor Sheave Dia. Motor Shaft Dia. No. of Belts Belt Make Belt Size Sheave Distance Fan Data CFM Fan RPM Fan Hz (VFD) Total S.P. Suction Total S.P. Discharge Total S.P. Amperage T1/T2/T3 Voltage Design GreenHeck QE1-18-1-30 04D11399 Preliminary 3 460 3 60 460 3.9 3 60 4.5 4" 1 1/2" 2 3VX530 CL ► CL 25" CL ► CL Design 4,970 1,310 N/A Final GREEN HECK QE1-18-1-30 04D11399 NA TOSHIBA 182-T 3 1788 60 460 3 3.9 4.485 BROWNING 3" 1 1/8 2 GATES 3VX530 21, +1-1 CL ► CL Preliminary 5,290 1,316 N/A 1 2.1 460 0.56 2.2 460 2.1 2.2 Final 5404 1343 NO VFD -0.43 0.07 0.5 2.3 460 2.1 Remarks: Note1: Preliminary Values taken from Oct. 2005 TAB report. Fan Sheave: 4" Shaft 1 1/2. The fan and motor speeds are actual speeds that were taken with a tachometer. The CFM for this fan was read with an air-foil and shortridge in the ductwork. The fan and motor sheave appear in TAB 2-03 Page 1 of 2 EXHAUST DUCT TRAVERSE REPORT National Center for Supercomputing Applica SYSTEM UNIT: Project: Loc./Zone: 1205 West Clark Street, Urbana, IL DATE: 6/9/2010 Readings Taken By: Charles Jenkins AIR DENSITY: 0.0745 Air Temp. in Duct: ºF 800 ALTITUDE: Multiple Duct Calc. ROUND DUCT #1: ROUND DUCT #2: ROUND DUCT #3: ROUND DUCT #4: ROUND DUCT #5: CFM DUCT #1: CFM DUCT #2: CFM DUCT #3: CFM DUCT #4: CFM DUCT #5: FPM DUCT #1: FPM DUCT #2: FPM DUCT #3: FPM DUCT #4: FPM DUCT #5: Total CFM Multiple Duct Calc. RECT. DIM. DUCT #1: RECT. DIM. DUCT #2: RECT. DIM. DUCT #3: RECT. DIM. DUCT #4: RECT. DIM. DUCT #5: CFM DUCT #1: CFM DUCT #2: CFM DUCT #3: CFM DUCT #4: CFM DUCT #5: FPM DUCT #1: FPM DUCT #2: FPM DUCT #3: FPM DUCT #4: FPM DUCT #5: Total CFM Grand Total CFM Design IN. IN. IN. IN. IN. Design "W X "W X "W X "W X "W X LB/CU.FT. FT. ↑ SEA LEVEL Preliminary IN. DIA. IN. DIA. IN. DIA. IN. DIA. IN. DIA. DIA. DIA. DIA. DIA. DIA. "H "H "H "H "H EF-3 24 Preliminary "W X 24 "W X "W X "W X "W X 5,404 "H "H "H "H "H Final IN. IN. IN. IN. IN. 24 Final "W X 24 "W X "W X "W X "W X 5,404 1,351 1,351 5,404 5,404 5,404 5,404 DIA. DIA. DIA. DIA. DIA. "H "H "H "H "H Remarks: TAB 2-03 Page 2 of 2 CONTROL DIAGRAMS & SEQ. 06 This section is dedicated to the control tradesmen who will need an understanding of the pneumatic and digital controls utilized in the building systems. Anything related to the sequence, logic block diagrams, alarms, sensors, and assigned points shall be contained herein. The actual, live data can be reached by following this link: TAC I/A Graphics
© Copyright 2024