Nexus 850 prisliste.

Montagevejledning Frese blandeventil MixCon
Anvendelse:
Tekniske data:
MixCon er en
skoldningssikret
blandeventil for varmt og
koldt vand.
Ved koldtvandsbrud
lukker ventilen for
varmtvandstilgangen
inden 4 sekunder.
Blandevandstemperaturen indstilles ved at dreje
plastgrebet mod "+" for
højere temperatur og
mod "-" for lavere
temperatur.
91697 vers. 2 August 07
Messing
ABS, sort.
Rustfri stål.
Voks.
EPDM.
Trykklasse
Max. tryk:
Min. tryk:
Max. trykforhold:
eller
10 bar.
0,2 bar.
5:1 (varmt:koldt
koldt:varmt)
Temperatur
Blandevandstemperatur:
Varmtvandstemperatur:
Koldtvandstemperatur:
30-60°C
50-80°C
05-30°C
Varm
Kold
For optimal skoldningssikring skal blandetemperaturen ligge
min. 10°C under varmtvandstemperaturen.
Godkendelse:
Mix
VA-godkendt.
Produktprogram/Målskema
Dim.
DN 20
DN 20
DN 20
Trykfaldsdiagram
Tilslutning
DN20/M/M/M*
Ø15/Cu-rør
Ø22/Cu-rør
Frese nr.
47-2643
47-2677
47-2688
VVS nr.
H1 [mm] H[mm] L[mm] Vægt [g]
723413.006
132
70
520
54
723414.005
139
88
690
61
723414.002
140
90
645
62
* 3/4" galv. rør
Tilbehør til nippel/nippel
Kontraventil
Ø15
Ø22
Tryk kPa
100
Frese nr.
38-0835
38-0834
VVS nr.
723414.815
723414.822
Kontraventilen skal
monteres i koldt- og
varmtvandstil-gangen, når
MixCon installeres i
brugsvandsinstallationer.
10
H
Dim
Alle MixCon blandeventiler er individuelt
testet og produceret i
henhold til
kvalitetsstyringssystemet ISO 9001 for at sikre
ensartet kvalitet og
funktionalitet.
Ventilhus:
Greb:
Fjedre:
Element:
O-ringe:
Dim.
Ventilens indstilling låses
ved at afmontere grebet
og dreje det 180°.
Derefter monteres grebet igen.
Montagevejledning Frese blandeventil MixCon
H1
H1
Dim.
L
Dim.
L
Snittegning af kontraventil
1
0,1
1
Flow l/s
Temp. varm:
Temp. kold:
Temp. blandet:
50°C
12°C
40°C
H
Mountinginstruction Frese Mixing Valve MixCon
Mountinginstruction Frese Mixing Valve MixCon
Application
Technical data:
MixCon is a fail-safe
mixing valve for hot
and cold water.
Valve body:
Control handle:
Springs:
Element:
O-rings:
Pressure range:
Max. pressure:
Min. pressure:
Max. Pressure ratio:
If the cold water fails
the valve shuts off the
hot water supply within
4 seconds.
91697 vers. 2 August 07
Hot
Cold
30-60°C
50-80°C
05-30°C
The optimum protection against scalding is achieved if the mixed water
temperature is at least 100C below the hot water temperature.
Approval:
Approved by the
Danish VA-Authorities
Mix
Productprogramme/Dimensions
Dim.
DN 20
DN 20
DN 20
Connection
DN20/fem/fem/fem*
Ø15/Cu-tube
Ø22/Cu-tube
Frese no. H1 [mm] H[mm] L[mm] Weight [g]
47-2643
132
70
54
520
47-2677
139
88
61
690
47-2688
140
90
62
645
Pressure
Trykfaldsdiagram
drop graph
* 3/4" galvanized pipe
Accessories for male/male
Non-return cartridge
Ø15
Ø22
Frese no.
38-0835
38-0834
Non-return cartridge must
be mounted on the hot and
cold inlet, when installed in
domestic water
installations.
10
H
Dim
Pressure kPa
100
Dim.
All MixCon mixing
valves are tested
separately and
produced in accordance
with the ISO 9001
Quality System to
ensure uniform quality
and functionality.
10 bar.
0,2 bar.
5:1
(Hot:cold or cold:hot)
Temperature
Mixed water temperature:
Hot water temperature:
Cold water temperature:
The mixed water
temperature is set by
turning the plastic
control handle towards
"+" to obtain higher
temperatures, and
towards "-" to obtain
lower temperatures.
The temperature
setting of the valve is
locked by dismantling
the handle and turning
it 180°. Then replace
the handle.
Brass CW602N
ABS, black
Stainless steel
Wax
EPDM.
H1
H1
Dim.
L
Dim.
L
Section view of Non-return cartridge
1
0.1
1
Flow l/s
Hot water temperature:
50°C
Cold water temperature: 12°C
Mixed water temperature: 40°C
H