Better Boilers www.ibcboiler.com

Better Boilers
www.ibcboiler.com
FEATURING OUR IBC SUPREME “SUPER COIL” 316TI
STAINLESS STEEL HEAT EXCHANGER.
From the factory in Vancouver, our uniquely designed and engineered Super Coil VFC Heat Exchanger is the best Heat Exchanger ever made. With more than
14 years of production excellence, utilizing the latest advances in burner, gas air mixing and control technology the “Super Coil” delivers the lowest flue gas
exhaust temperature / return water temperature differential.
VFC 15-150
15,000 to 150,000 BTU/H
VFC 45-225
45,000 to 225,000 BTU/H
 New Touch Screen Boiler Controller
Express setup
Remote monitoring & diagnostics
Easy USB programmability
True native BACnet
Intuitive alert system
Easy homeowner DHW temp adjust
 VFC 15-150 became the first and industry
leading 10:1 turndown ratio residential-scale
modulating boiler in North America. Span the
range from small cottage to sprawling
mansion.
 Sustained high efficiency across firing range
even at high temperatures
 Built-in
4-load
priority
management
and
switching
 Unmatched durability from our exclusive 316Ti
stainless steel
exchanger
80psi
“Super
Coil”
heat
 Control 5 independent pumps directly from the
boiler without additional relays
 Contractor friendly with easy to use controls,
wiring and serviceability
 Go anywhere venting options up to 480 feet!
Specifications
VFC 15-150
VFC 45-225
CSA Input (Natural Gas or Propane *) - MBH
15 - 150
45 - 225
CSA Input (Natural Gas or Propane *) - KW
4.4 - 44
13 - 66
CSA Output - MBH
14 - 139
12 - 60
CSA Output - KW
4.1 - 41
12.7 - 70.0
A.F.U.E
95.00%
95.00%
Min gas pressure (Nat. Gas or Propane) - inch w.c.
5
5
Max gas pressure (Nat. Gas or Propane) - inch w.c.
14
14
Power (120Vac/60Hz) - Watts @ full fire - Watts
57
57
Weight (empty) - lbs/Kg
150 / 68
153 / 70
Pressure vessel water content – USG/Liters
2.4 / 9
2.4 / 9
Max boiler flow rate - USgpm
4
8
Min boiler flow rate - USgpm
16
25
Max operating pressure - psig
80
80
Min water pressure - psig
8
8
Normal flue temp @ 160°F boiler return water temp - High Fire
100°F to 105°F
100°F to 105°F
Normal flue temp @ 160°F boiler return water temp - High Fire
160°F to 165°F
160°F to 165°F
Approved installation altitude - ASL
0 - 12,000 ft
0 - 12,000 ft
Ambient temperature - Low (°F/°C)
32°F / 0°C
32°F / 0°C
Ambient temperature - High (°F/°C)
122°F / 50°C
122°F / 50°C
Max relative humidity (non-condensing)
90.00%
90.00%
Min water Temperature (°F/°C)
34°F / 1.1°C
34°F / 1.1°C
Max water Temperature (electronic-limit) (°F/°C)
190°F / 87.7°C
190°F / 87.7°C
Max water Temperature (mechanical hi-limit) (°F/°C)
200°F / 93.3°C
200°F / 93.3°C
Max Δ T - supply / return (electronic fence)
36°F
35°F
Maximum equivalent vent length each side
2”
50'
N/A
Maximum equivalent vent length each side
3”
120'
240'
(Natural Gas or Propane)
Air intake options: either direct vent or indoor supply
Ships with 30psi relief valve
IBC boilers are not de-rated because of longer
vent runs
 Better efficiency 95% AFUE
Exhaust pipe size
Maximum equivalent length
Sched.40; Rigid PPs
2” (15-150 only)
50’ (each side)
2 1/2” (15-150 only)
70’
Venting up to 480 Feet!
3” (15-150)
120’
240’ Exhaust + 240’ Intake
3” (45-225)
240’
90° vent elbow
Allow 8’ equivalent
45° elbow
Allow 3’ equivalent
PP’s 87-90° elbows
Allow 8’ equivalent
Flexible PPs
2” Flexible
60’ (see note 1)
3” Flexible
60’ (see note 2)
www.ibcboiler.com
VFC Series
PREMIER CONDENSING BOILERS
Automated laser welding now underway
SL SERIES - BETTER INSTALLATION FLEXIBILITY
Made of high grade 439 stainless steel the SL Heat Exchangers deliver 95% AFUE efficiency. The SL Heat Exchangers are easy to inspect and features a
condensate draining system that cleans as it heats. With more models and now featuring our new IBC Touch Screen Boiler Control you get all the features
of our 5 button control with the following added features: Express Set Up, Easier Diagnostics & Intuitive Alert System with plain English warnings & error
messages. There is an SL model for every application.
SL 20-115G2
28,000 to 160,000 BTU/H
Supply
RESIDENTIAL CONDENSING BOILERS
With Supply and Return connections on
both sides of the boiler your installation
can’t get any easier. Use the left side, the
right side or both. The choice is yours.
 New Touch Screen Boiler Controller
Express setup
Remote monitoring & diagnostics
Easy USB programmability
True native BACnet
Intuitive alert system
Easy homeowner DHW temp adjust
 Built-in 4-load priority management and
switching
 Connect your IBC Indirect Water Tank
directly to the boiler without a primary loop
 Industry leading turndown ratio of 5.75 : 1
means you have the power to heat your
home in the coldest weather yet reduce short
cycling when the weather is mild
 Built-in outdoor reset control of water
temperature
 Better efficiency 95% AFUE
Specifications
SL 20-115G2
CSA Input (Natural Gas or Propane *) - MBH
20 - 115
28 - 160
CSA Input (Natural Gas or Propane *) - KW
6 - 34
8.2 - 47
CSA Output - MBH
19 - 109
26.2 - 147
CSA Output - KW
5.5 - 32
7.7 - 43
A.F.U.E
95.0%
95.0%
Min gas pressure (Nat. Gas or Propane) - inch w.c.
5
5
Max gas pressure (Nat. Gas or Propane) - inch w.c.
14
14
Power (120Vac/60Hz) - Watts @ full fire - Watts ( without pumps) 54
73
Weight (empty) - lbs/Kg
85/39
102 / 46.3
Pressure vessel water content – USG/Liters
2.9 / 11
3.2 / 12.2
Max boiler flow rate - USgpm
14
19
Min boiler flow rate - USgpm
2
4
Max operating pressure - psig
30
30
Min water pressure - psig
8
8
Approved installation altitude - ASL
0 - 12,000 ft
0 - 12,000 ft
Ambient temperature - Low (°F/°C)
32°F / 0°C
32°F / 0°C
Ambient temperature - High (°F/°C)
122°F / 50°C
122°F / 50°C
Max relative humidity (non-condensing)
90.00%
90.00%
Min water Temperature (°F/°C)
34°F / 1.1°C
34°F / 1.1°C
Max water Temperature (electronic-limit) (°F/°C)
190°F / 87.8°C
190°F / 87.8°C
Max water Temperature (mechanical hi-limit) (°F/°C)
200°F / 93.3°C
200°F / 93.3°C
Max Δ T - supply / return (electronic fence)
40°F
40°F
SL 28-160
Maximum equivalent vent length, each side
2”
100'
35'
Maximum equivalent vent length, each side
3”
240'
170'
Return
(Natural Gas or Propane)
Air intake options: either direct vent or indoor supply
Ships with 30psi relief valve
 Very low water side and combustion side
pressure drops
 Venting up to 480 feet on the SL 20-115G2
 Left and right clearance as low as 1”
 Limited lifetime residential warranty
Exhaust pipe size
Maximum equivalent length
SL 20-115G2
SL 28-160
2”
100’
35’
3”
240’
170’
90° long sweep elbow
Allow 5’ equivalent
Allow 5’ equivalent
90° vent elbow
Allow 8’ equivalent
Allow 8’ equivalent
45° elbow
Allow 3’ equivalent
Allow 3’ equivalent
PPs 87-90° elbows
Allow 8’ equivalent
Allow 8’ equivalent
Sched.40; Rigid PPs
Flexible PPs
2” Flexible
45’ (max) lineal x 1.4 = equivalent
3” Flexible
45’ (max) actual lineal x 1.2 = equivalent
Supply
98’ (max) actual lineal x 1.2 = equivalent
www.ibcboiler.com
Return
SL Series
20,000 to 115,000 BTU/H
SL 28-160
SL 35-199
SL 45-260
35,000 to 199,000 BTU/H
45,000 to 260,000 BTU/H
New to the SL Series the SL 35-199
expands the capacity of the former
SL 30-175 and with the new IBC touch
screen controller offers the most flexible
control option on the market.
 New Touch Screen Boiler Controller
Express setup
Remote monitoring & diagnostics
Easy USB programmability
True native BACnet
Intuitive alert system
Easy homeowner DHW temp adjust
 Built-in 4-load priority management and
switching
 LWCO options available
 Bottom piping connections for easy network
piping
 Better installation flexibility
 Connect your IBC Indirect Water Tank directly
to the boiler without a primary loop
means you have the power to heat your home
in the coldest weather yet reduce short cycling
when the weather is mild
outdoor
temperature
reset
control
SL 35 -199
SL 45 - 260
CSA Input (Natural Gas or Propane *) - MBH
35 - 199
45 - 260
CSA Input (Natural Gas or Propane *) - KW
10.3 - 58.3
13.2 - 76.2
CSA Output - MBH
32.7 - 181.3
43.2 - 239
CSA Output - KW
7.7 - 43
12.7 - 70.0
A.F.U.E
95.00%
95.00%
Min gas pressure (Nat. Gas or Propane) - inch w.c.
5
5
Max gas pressure (Nat. Gas or Propane) - inch w.c.
14
14
Power (120Vac/60Hz) - Watts @ full fire - Watts
92
127
Weight (empty) - lbs/Kg
151 / 69
162 / 74
Pressure vessel water content – USG/Liters
5 / 19
5 / 19
Max boiler flow rate - USgpm
25
25
Min boiler flow rate - USgpm
6
6
Max operating pressure - psig
30
30
Min water pressure - psig
8
8
Approved installation altitude - ASL
0 - 12,000 ft
0 - 12,000 ft
Ambient temperature - Low (°F/°C)
32°F / 0°C
32°F / 0°C
Ambient temperature - High (°F/°C)
122°F / 50°C
122°F / 50°C
Max relative humidity (non-condensing)
90.00%
90.00%
Min water Temperature (°F/°C)
34°F / 1.1°C
34°F / 1.1°C
Max water Temperature (electronic-limit) (°F/°C)
190°F / 88°C
190°F / 88°C
Max water Temperature (mechanical hi-limit) (°F/°C)
200°F / 93.°C
200°F / 93.°C
Max Δ T - supply / return (electronic fence)
40°F
40°F
Maximum equivalent vent length each side
3”
200'
200'
Maximum equivalent vent length each side
4”
200'
200'
(Natural Gas or Propane)
 Industry leading turndown ratio of 5.75 : 1
 Built-in
Specifications
of
water
Air intake options: either direct vent or indoor supply
Ships with 30psi relief valve
Exhaust pipe size
Maximum equivalent length
Sched.40; Rigid PPs
 Better efficiency 95% AFUE
3”
200’
 Very low water side and combustion side
4”
200’
90° long sweep elbow
Allow 5’ equivalent
90° vent elbow
Allow 8’ equivalent
45° elbow
Allow 3’ equivalent
PP’s 87-90° elbows
Allow 8’ equivalent
pressure drops
 Venting up to 400 feet
Flexible PPs
3” Flexible (SL 35-199)
160’ (max) lineal x 1.2 = equivalent
3” Flexible (SL 45-260)
60’ (max) lineal x 3.33 = equivalent
4” Flexible
160’ (max) lineal x 1.2 = equivalent
www.ibcboiler.com
SL Series
CONDENSING BOILERS
SL 80-399
80,000 to 399,000 BTU/H
COMMERCIAL CONDENSING BOILER
In today’s energy conscious world choosing the right heating system is crucial to maximizing a
buildings energy savings and environmental impact. The cost effective solution to any application.
Whether the application is a retrofit or new construction combining the SL 80-399 boiler with the
flexibility of the Multiplex Racking Systems and IBC’s new touchscreen controller the options
available are endless.
 New Touch Screen Boiler Controller
Express setup
Remote monitoring & diagnostics
Easy USB programmability
True native BACnet
Intuitive alert system
Easy homeowner DHW temp adjust
 Multi boiler communication up to 9.5 million Btuh
(24 boilers) without additional controls
 With 24 boilers turndown ratio is 120:1 = min.
firing rate range is 80,000 Btu/h all the way up to
9.5 million Btu/h in 1000 Btu/h increments
 DDC Control 0-10 VDC or 4-20 mA without
additional controls
 95.7% Efficiency - CSA 4.9 - 2010
 Optional 316 Ti titanium heat exchanger
 Built-in
4-load
priority
management
and
switching
23.4 - 117
CSA Output - MBH
77 - 382
CSA Output - KW
22.6 - 112
Combustion Efficiency (CSA 4.9—2010)
95.7%
Min gas pressure (Nat. Gas or Propane) - inch w.c.
5
Max gas pressure (Nat. Gas or Propane) - inch w.c.
14
Power (120Vac/60Hz) - Watts @ full fire - Watts ( without pumps)
345
Weight (empty) - lbs/Kg
240 / 110
Pressure vessel water content – USG/Liters
7 / 26
Max boiler flow rate - USgpm
45
Min boiler flow rate - USgpm
20
Max operating pressure - psig
80
Min water pressure - psig
8
Approved installation altitude - ASL
0 - 12,000 ft
Ambient temperature - Low (°F/°C)
32°F / 0°C
Ambient temperature - High (°F/°C)
122°F / 50°C
Max relative humidity (non-condensing)
90.00%
Min water Temperature (°F/°C)
34°F / 1°C
Max water Temperature (electronic-limit) (°F/°C)
190°F / 87.7°C
Max water Temperature (mechanical hi-limit) (°F/°C)
200°F / 93.3°C
Max Δ T - supply / return (electronic fence)
40°F
reset
control
4”
200'
(Natural Gas or Propane)
Air intake options: either direct vent or indoor supply
 Industry leading turndown ratio of 5:1
outdoor
temperature
80 - 399
CSA Input (Natural Gas or Propane *) - KW
Maximum equivalent vent length, each side
 DHW opt out priority for multi boiler systems
 Built-in
SL 80-399
CSA Input (Natural Gas or Propane *) - MBH
Ships with 30psi relief valve
of
water
Exhaust pipe size
Maximum equivalent length
 Venting up to 400 feet
Sched.40; Rigid PPs
4”
200’
 Various Multiplex Racking & rack only options
90° long sweep elbow
Allow 8’ equivalent
90° vent elbow
Allow 5’ equivalent
45° elbow
Allow 3’ equivalent
PPs 87-90° elbows
Allow 8’ equivalent
available
Flexible PPs
4” Flexible
160’ (max) actual lineal x 1.2 = equivalent
www.ibcboiler.com
SL Series
Specifications
Menu
Express Setup
Load Status
User Setup
Installer Setup
Diagnostics
Back
IBC
04:30
ADVANCED CONTROL TECHNOLOGY
At IBC we are dedicated to finding new and better ways to provide superior comfort and fuel savings to our customers. We are pleased to announce that all
IBC boilers in the SL & VFC Series will be equipped with our new Touch Screen Boiler Controller featuring the latest in advanced touch screen technology
and software features.
V-10
TOUCH
SCREEN
CONTROLLER
Available in all VFC & SL Series Boilers
IBC CONTROL AT YOUR FINGERTIPS
Building on the success of our 5 button boiler control launched in 2003, the new touch screen control makes it even
easier to setup and monitor your IBC Boiler. With intuitive features like Express Setup, Easier Diagnostics & Intuitive
Alert System with plain English Warnings & Error Messages your VFC or SL Series boiler has never been easier to
use interface than ever before.
EXPRESS SETUP
 Program your boiler in seconds with an
interview style quick start menu
 User friendly interface for contractor and home
owner
COMPLETE REMOTE ACCESS
 Built in internet connectivity. Monitor your
boilers operation in real time from your PC/
Mac
 Remote monitoring & diagnostics
TRUE NATIVE BACnet
 Seamlessly integrate IBC BACnet enabled
boilers into your current building automation
system
MORE FLEXIBILITY
 Intuitive alert system with
warnings & error messages
plain
Home Page Screen
Main Menu
Express Setup
Load combining features
Immediate input feedback
Color coded error notifications
English
 Ability to manage up to 4 different loads and 5
pumps
 Build in alarm notification relay
 Automatic altitude adjustment
 Pre programmed values for all load types
www.ibcboiler.com
Controls
EASY USB PROGRAMMABILITY
 USB Port for emailing of software updates and
multi boiler setup
HC 13-50
13,500 to 51,000 BTU/H
HC 23-84
23,000 to 84,000 BTU/H
29,000 to 106,000 BTU/H
HC 33-160
HC 33-124
33,000 to 124,000 BTU/H
HC 29-106
33,000 to 160,000 BTU/H
CONDENSING BOILERS
Introducing IBC’s smallest ever boiler, the HC series begins with the HC13-50 offering the solution for
todays better insulated buildings. With onboard full outdoor reset and a slim boiler room footprint the HC
Series offers great value for money without sacrificing reliability.
 Unique and innovative single pass copper heat
exchanger, ensuring greater efficiency and
eliminating water side corrosion
 Up to 95% AFUE, with full ASME rated vessel
 Built in boiler pump
 2” & 3” venting options available
 Contractor friendly, easy to install, maintain
Specification
HC 13-50
HC 23-84
HC 29-106
HC 33-124
HC 33-160
 Fewer parts ensuring greater reliability
CSA Input (Natural Gas or Propane) – MBH
13.5 – 51
23 – 84
28.5 – 106
33 – 124
33 – 160
CSA Input (Natural Gas or Propane) – KW
3.95 – 14.94
6.7 – 24.9
8.4 – 31.0
9.7 – 36.3
9.7 – 46.9
 Outdoor reset technology increases efficiency
CSA Output – MBH
12.4 – 45.4
21 – 79
26 – 99
31 – 115
30 – 149
CSA Output - KW
3.64 – 13.3
6.3 – 23.0
7.8 – 28.9
9.0 – 33.8
9.0 – 43.6
A.F.U.E
95.00%
94.00%
94.00%
94.00%
94.00%
Min Gas Pressure (Nat. Gas or Propane) – inch w.c.
5
5
5
5
5
Max Gas Pressure (Nat. Gas or Propane) – inch w.c.
14
14
14
14
14
Power (120Vac/60Hz) - Watts @ full fire with internal pump 126
126
128
130
164
Weight (empty) – lbs/Kg
85 / 39
85 / 39
85 / 39
85 / 39
85 / 39
Pressure Vessel water content – USG/Liters
0.37/1.4
0.37/1.4
0.37/1.4
0.5/1.9
0.5/1.9
Max boiler flow rate - USgpm
9
9
10
11
11
Min boiler flow rate - USgpm
2
2
3
3
3
Max Operating Pressure – Space Heating Coil - psig
43.5
43.5
43.5
43.5
43.5
Approved installation altitude - ASL
12,000 ft
12,000 ft
12,000 ft
12,000 ft
12,000 ft
Ambient Temperature – Low (°F/°C)
32/0
32/0
32/0
32/0
32/0
Ambient Temperature – High (°F/°C)
122/50
122/50
122/50
122/50
122/50
Max relative humidity (non-condensing)
90.00%
90.00%
90.00%
90.00%
90.00%
Min water Temperature - Space Heating (°F/°C)
50/20
50/20
50/20
50/20
50/20
Max water Temperature – Space Heating (°F/°C)
194/90
194/90
194/90
194/90
194/90
Max equivalent vent length 3" (each side)
120'
120'
120'
120'
120'
Max equivalent vent length 2" (each side)
35'
35'
35'
35'
35'
by lowering the water temp automatically
 10 year limited warranty
 Reset heating - Set point - DHW
 Includes Air Vent, Outdoor Sensor & Relief
Valve
 Exceptional value
 Better reliability and durability
www.ibcboiler.com
HC Series
and service
DC 23-84
23,000 to 84,000 BTU/H
DC 29-106
33,000 to 124,000 BTU/H
DC 33-160
DC 33-124
33,000 to 124,000 BTU/H
33,000 to 160,000 BTU/H
DUAL CONDENSING COMBI BOILERS
At long last on demand DHW joins the IBC boiler lineup. Combining Domestic Hot Water & Space
Heating in a single compact design, the DC Series offers a tried and true heat exchanger design. With
the DHW comfort mode, the “cold water sandwich” is eliminated with no moving parts.
 ASSE
1070 Certified high performance
DHW Thermostatic Mixing Valve included
 Built in Boiler Pump
Specification
DC 23-84
DC 29-106
DC 33-124
DC 33-160
CSA Input (Natural Gas or Propane) – MBH
23 – 84
28.5 – 106
33 – 124
33 – 160
CSA Input (Natural Gas or Propane) – KW
6.7 – 24.9
8.4 – 31.0
9.7 – 36.3
9.7 – 46.9
CSA Output – MBH
21 – 79
26 – 99
31 – 115
30 – 149
CSA Output - KW
6.3 – 23.0
7.8 – 28.9
9.0 – 33.8
9.0 – 43.6
DHW - CSA Input (Natural Gas or Propane) - MBH
23 - 84
28.5 - 106
33 - 124
33 - 124
DHW - CSA Input (Natural Gas or Propane) - KW
6.7 - 24.9
8.4 - 31.0
9.7 - 36.3
9.7 - 36.3
A.F.U.E
94.00%
94.00%
94.00%
94.00%
Min Gas Pressure (Nat. Gas or Propane) – inch w.c.
5
5
5
5
Max Gas Pressure (Nat. Gas or Propane) – inch w.c.
14
14
14
14
Power (120Vac/60Hz) - Watts @ full fire with internal pump
126
128
130
164
Weight (empty) – lbs/Kg
85 / 39
85 / 39
85 / 39
85 / 39
Pressure Vessel water content – USG/Liters
0.37/1.4
0.37/1.4
0.5/1.9
0.5/1.9
Max boiler flow rate - USgpm
9
10
11
11
Min boiler flow rate - USgpm
2
3
3
3
Max Operating Pressure – Space Heating Coil - psig
43.5
43.5
43.5
43.5
Max Operating Pressure – Domestic Hot Water Coil - psig
150
150
150
150
 Left and right clearance as low as 1”
Approved installation altitude - ASL
12,000 ft
12,000 ft
12,000 ft
12,000 ft
Ambient Temperature – Low (°F/°C)
32/0
32/0
32/0
32/0
 10 year limited warranty
Ambient Temperature – High (°F/°C)
122/50
122/50
122/50
122/50
Max relative humidity (non-condensing)
90.00%
90.00%
90.00%
90.00%
Min water Temperature - Space Heating (°F/°C)
50/20
50/20
50/20
50/20
Max water Temperature – Space Heating (°F/°C)
194/90
194/90
194/90
194/90
Min water Temperature – Domestic Hot Water (°F/°C)
104/40
104/40
104/40
104/40
Max water Temperature – Domestic Hot Water (°F/°C)
149/65
149/65
149/65
149/65
Min flow rate to activate DHW heating - USgpm
0.5
0.5
0.5
0.5
Max flow rate DHW heating - USgpm
2.6
3.3
4
4
Max equivalent vent length 3" (each side)
120'
120'
120'
120'
2.7 GPM
3.2 GPM
3.2 GPM
 Includes Air Vent, Outdoor Sensor & Relief
Valve
 The dual two in one, back to back heat
exchanger eliminates the need for a diverter
valve and secondary domestic hot water plate
heat exchanger
 Contractor friendly, fewer internal parts, easy
to install, maintain and service
 Reset heating - Set point - DHW
 Outdoor
Reset Technology increases
efficiency by lowering the water temp
automatically
 Unique “self learning” ECO-mode for greater
DHW efficiencies
Domestic Hot Water Delivery: @70° / 39°C temperature rise 2.1 GPM
www.ibcboiler.com
DC Series
 94% AFUE with full ASME rated vessel
MULTI-PLEX
Racking
Designed for the SL 80-399
ENGINEERED ● EASY TO INSTALL ● TURNKEY
A Modular system for commercial and multi family installation the Multiplex racking system components fit through
standard doorways reducing the need for heavy transport equipment. Our easy to set up boiler networks also
provide for precise load matching through wide turndown ratios.
SPECIFICATIONS
SYSTEM INCLUDES
 Freestanding inline or back to back options
 Header sizes include: 3”, 4” or 6”
 Left or right header connections includes I set
of blind flanges
 Combination from 2 to 12 boilers on one
Multiplex racking system
Part No.
Width "/ mm
IN LINE RACK
Height " / mm
Depth "/ mm
3" Header
2 Boiler In-line
3 Boiler In-line
90-151
70" / 1778 mm
76.25" / 1937 mm
35.5" / 902 mm
90-149
102" / 2590 mm
76.25" / 1937 mm
35.5" / 902 mm
4" Header
2 Boiler In-line
90-159
70" / 1778 mm
76.25" / 1937 mm
35.75" / 908 mm
3 Boiler In-line
90-160
102" / 2590 mm
76.25" / 1937 mm
35.75" / 908 mm
4 Boiler In-Line
90-161
134" / 3404 mm
76.25" / 1937 mm
35.75" / 908 mm
5 Boiler In-Line
90-162
166" / 4217 mm
76.25" / 1937 mm
35.75" / 908 mm
6 Boiler In-Line
90-163
198" / 5030 mm
76.25" / 1937 mm
35.75" / 908 mm
4 Boiler In-line
90-171
134" / 3404 mm
76.25" / 1937 mm
38" / 965 mm
5 Boiler In-line
90-178
166” / 4217 mm
76.25” / 1937 mm
38” / 965 mm
6 Boiler In-line
90-164
198" / 5030 mm
76.25" / 1937 mm
38" / 965 mm
6" Header
8 Boiler In-line
90-165
262" / 6656 mm
76.25" / 1937 mm
38" / 965 mm
10 Boiler In-line
90-166
326" / 8280 mm
76.25" / 1937 mm
38" / 965 mm
12 Boiler In-line
90-176
390" / 9906 mm
76.25" / 1937 mm
38" / 965 mm
 Flow switches, external sensors optional
 Low Loss Header options: 3”, 4” or 6”
 Compact Design: Easy to get into small
spaces around existing equipment
 Low Head Loss—Better flow rates
 Seismic ratable
BACK TO BACK RACK
4" Header
2 + 2 Boiler Back to Back
90-167
70" / 1778 mm
76.25" / 1937 mm
58.5" / 1486 mm
3 + 3 Boiler Back to Back
90-168
102" / 2590 mm
76.25" / 1937 mm
58.5" / 1486 mm
3 + 3 Boiler Back to Back
90-169
102" / 2590 mm
76.25" / 1937 mm
60.5” / 1537 mm
4 + 4 Boiler Back to Back
90-170
134" / 3404 mm
76.25" / 1937 mm
60.5” / 1537 mm
5 + 5 Boiler Back to Back
90-172
166" / 4217 mm
76.25" / 1937 mm
60.5” / 1537 mm
6 + 6 Boiler Back to Back
90-177
198” / 5030 mm
76.25” / 1937 mm
60.5” / 1537 mm
6" Header
 Rack only options also available
SPECIFICATIONS - Racking only
 Easy 1 day installation
Racking Only
Part No.
Width " / mm
Height " / mm
Depth” / mm
1 Boiler Rack
R-137
38" / 965 mm
76.25" / 1937mm
26.5" / 673 mm
 Approximate assembly time for 4 x SL 80-399
2 Boiler Rack
R-138
70" / 1778 mm
76.25" / 1937mm
26.5" / 673 mm
3 Boiler Rack
R-136
102" / 2590 mm
76.25" / 1937mm
26.5" / 673 mm
4 Boiler Rack
R-139
134" / 3404mm
76.25" / 1937mm
26.5" / 673 mm
5 Boiler Rack
R-140
166" / 4217 mm
76.25" / 1937mm
26.5" / 673 mm
6 Boiler Rack
R-134
198" / 5030 mm
76.25" / 1937mm
26.5" / 673 mm
7 Boiler Rack
R-141
230" / 5843 mm
76.25" / 1937mm
26.5" / 673 mm
8 Boiler Rack
R-142
262" / 6656 mm
76.25" / 1937mm
26.5" / 673 mm
x 2 men = 8 Hours
www.ibcboiler.com
RACKING
Pumps: Model - UPS 43-44F
Isolation ball valves - Check valves
Welded steel headers - Connecting piping
Flexible stainless steel connectors
Boiler drains - Optional accessories available
Multiplex Racking System
30 TO 115 GALLON
30, 40, 50, 60, 80, 115 Gallon
INDIRECT WATER HEATERS
High performance domestic hot water made of 316L stainless steel. Ships with a domestic
hot water sensor ready to communicate with any VFC or SL Series boiler.
Durable stainless steel
 Top connections for easy installation
on selected models
 High out put options & large pipe connections
available on selected models
 High capacity smooth wall coils which are
resistant to airlocks
 Durable high grade 316L stainless steel
loss
 A thermoplastic jacket that will not corrode
 Optional Honeywell control for additional
flexibility and easy service
 Quality brass ball valve style drain and T+P
DOMESTIC WATER BOILER WATER
IN/OUT
IN/OUT
MAXIMUM
WORKING
PRESSURE (PSI)
APPROX.
SHIPPING
WEIGHT
IBC 30
34
23.5
3/4
1
150
85
IBC 40
44
23.5
3/4
1
150
100
IBC 40L
36
28.0
3/4
1
150
100
IBC 50
54
23.5
3/4
1
150
110
IBC 60
62
23.5
3/4
1
150
125
IBC 60L
46
28.0
3/4
1
150
120
IBC 80
56
28.0
1
1
150
140
IBC 115
74
28.0
1
1
150
175
MODEL
 Fail proof, welded stainless steel dip tube
 A full 2” of insulation for an extremely low heat
PIPING CONNECTIONS NPT
DISMETER
INCHES
HIGH OUTOUT UNITS
IBC 80-HO
56
28.0
1
1
150
155
IBC 115-HO
74
28.0
1
1
150
190
IBC 80-HOC
56
28.0
1 1/2
1 1/4
150
155
IBC 115-HOC
74
28.0
1 1/2
1 1/4
150
190
Note: All ratings are based on 180 degree F boiler cold water inlet. For 160 degree F boiler water
supply multiply ratings by 0.86. In the interest of continuous improvement, specifications are subject
to change without notice.
valves are factory installed
MAX. FIRST HOUR RATING
GAL/Hr @
 Conforms to UL STD 174, Certified to CAN/
CSA STD C22.2 No. 110-94
CONTINOUS RATING
GAL/HR@
140F
115F
140F
115F
MODEL
BOILER
OUTPUT
REQUIRED
BTU/HR)
MIN BOILER
PRESSURE
WATER FLOW DROP THROUGH
THROUGH COIL
COIL (FT.
WATER))
 Limited lifetime residential warranty
IBC 30
168
223.0
144
200
125,600
14.0
5.3
IBC 40
185
244.0
165
213
134,200
14.0
5.7
 Call IBC for special order on storage & buffer
IBC 40L
168
2223.0
144
200
125,600
14.0
5.3
IBC 50
201
265.0
163
226
129,900
14.0
6.0
IBC 60
218
286.0
172
240
151,000
14.0
6.2
IBC 60L
200
260.0
154
213
134,100
14.0
5.7
IBC 80
229
293.0
1167
231
145,600
14.0
6.0
IBC 115
274
347.0
186
258
162,400
14.0
6.6
tanks.
High outout units
IBC 80-HO
332
436.0
270
374
235,600
14.0
9.9
IBC 115-HO
378
488.0
289
400
251,700
14.0
10.5
IBC 80-HOC
351
462.0
289
400
251,700
21.0
15.8
IBC 115-HOC
387
501.0
298
413
259,800
21.0
16.7
www.ibcboiler.com
Series
SL
TANKS
 Low profile height available for small spaces
DIMENTIONS
HEIGHT INCHES
Condensate Neutralization Tank
Part# 180-048 / Refill Kit Part# 180-049
This unit is ideal for neutralizing condensate from condensing boilers. Condensate is acidic and has the potential to harm
the environment and the sewer system. This neutralization tank will neutralize the condensate to a neutral pH level before it
is discharged to the drain.
 Neutralized condensate will not corrode drain and sewer systems or harm the environment
 Fast and easy installation
 Fully removable lid allowing for ease of service
 20 liter (5.3 US gallon) reservoir for large capacity neutralization
 Comes with initial charge of neutralizing agent
 Suitable for boiler packages up to 7.0 MBTU
180-048 Condensate Neutralization Tank
Intake Air Filters
Part# SC-100A: VFC Series, SL 20-115, SL 28-160
Part# P-172: SL 35-199, SL 45-260, SL 80-399
Combustion fan and burner blockages can occur when environmental particulates and
foreign matter contaminants (leaves, dust, dandelion & cottonwood fluff, etc.) are drawn
into the air intake. In areas where this problem is suspected to be an issue, our optional
air intake filter should be installed.
 Both can be orientated in a variety of positions
 Easily cleaned by vacuuming or brushing
 Replacement elements available
 See our website for more detailed information on Air Filters.
P-172 Air Intake Filter mounted directly
onto an SL 80-399 boiler
www.ibcboiler.com
ACCESSORIES
 New design allows for greater condensate flow while providing superior neutralization
APPLICATION DRAWINGS
For further application drawings see our website at www.ibcboiler.com
www.ibcboiler.com
IBC Technologies Inc. (Head Office)
1445 Charles Street
Vancouver, BC, Canada V5L 2S7
Tel: 604-877-0277
Fax: 604-877-0295
[email protected]
www.ibcboiler.com
IBC USA
4203 Industrial Court
Sheboygan, WI, USA 53083
Tel: 920-783-8340
Better Boilers
Fax: 920-783-8339
Nov 2014
All information contained in the brochure is subject to change without notice