NOTES FOR PCM, US-NATION-WIDE, GENERIC, PV, STRUCTURAL INSTALLATION
THIS SEALED PLAN CONFORMS TO: ASCE 7-10; INTERNATIONAL BUILDING CODE (IBC) 2010 - PLUS EARLIER VERSIONS; STATE BUILDING CODES
BASED UPON IBC - FLORIDA 2010 FBC IN PARTICULAR.
THIS PLAN IS:
• INTENDED FOR THE STRUCTURAL ATTACHMENT OF ANY AND ALL APPROVED PV MODULES OF STANDARD LENGTH & WIDTH DIMENSIONS AND
PROPORTIONS.
• INTENDED FOR USE WITH ROOF COVERINGS OF ALL TYPES AND ON ALL ROOF SLOPES FROM FLAT THRU 12-IN-12 AT ROOF HEIGHTS OF 60-FT
OR LESS WITHIN US.
• SHALL ONLY BE USED FOR PV INSTALLATIONS UTILIZING PCM RAILS & SPECIFIED HARDWARE. THIS PLAN SHALL ONLY BE USED FOR MOUNTING
PV MODULES:
• THE DETAILS SPECIFIED ON THIS “PAPER” PLAN ARE CONSIDERED TO BE THE MINIMUM NEEDED BY AHJ AND INSTALLERS. USERS ARE
ENCOURAGED TO ACCESS AN EV (ELECTRONIC VERSION) OF THIS PLAN AT WWW.GEZELMANPE.COM/PV/0203P.PCM10_US.PDF . HYPERLINKS
ARE EMBEDDED IN EV WHICH PROVIDE EASY ACCESS TO SUPPLEMENTAL OEM, GOVERNMENTAL, AND OTHER INFORMATION SOURCES OF
VALUE. EV ALSO ALLOWS VIEWER TO STUDY THE PLAN AT A MAGNIFICATION OF HIS CHOICE UP TO 6400%. IF A CONFLICT SHOULD OCCUR
BETWEEN THE SPECIFICATIONS HEREON AND AN OEM DETAIL, OEM SHALL PREVAIL.
MOUNTING LIMITATIONS:
1. ROOF PRESSURE ZONE 3 (PZ-3) SHALL NOT BE USED WITHIN MIAMI-DADE. OUTSIDE MIAMI-DADE, PZ3 MAY BE USED WITH AN EOR (ENGINEER OF
RECORD) SPECIAL REQUEST, SEALED, LETTER WHICH SHALL PROVIDE DETAILS FOR SITE-SPECIFIC ADAPATION OF THIS PLAN. PZ1 & PZ2 MAY BE
USED ANYWHERE IAW (IN ACCORDANCE WITH) PCM RAIL SPACING SPECIFIED IN FIGURE 02 THIS PLAN.
2. PV MODULES SHALL BE MOUNTED PARALLEL WITH ROOF (AND WITHIN A FEW INCHES) OR TILTED UP AT NOT GREATER THAN (NGT) 15-DEGREES
FROM THE HORIZONTAL .
3. THOSE DESIRING THAT EOR PROVIDE PLANS FOR CONDITIONS OTHER THAN HEREIN STATED, AND/OR RACKING OTHER THAN PCM, AND/OR
INSTALLATION IN ROOF PRESSURE ZONES OTHER THAN PZ1 & PZ2, AND/OR TILT-UP GREATER THAN 15-DEGREES ABOVE THE ROOF PLANE, AND/OR
INSTALLATIONS OUTSIDE OF US, AND/OR ELECTRICAL DESIGN, ARE REQUESTED TO CONTACT E0R DIRECTLY-OFFICE: 813 909 1956, E-MAIL:
[email protected]
STRUCTURAL:
· SEISMIC - THIS PLAN IS EXEMPT IAW SUB-PARAGRAPH 6 OF ASCE 7-10 PARAGRAPH 13.1.4
· SNOW - SPECIFIED MATERIALS & METHODS ARE SUFFICIENTLY STRONG TO ACCOMODATE SNOW LOADS OF 10-PSF AND UNDER USING PCM RAIL
ATTACHMENT SPACING
SPECIFIED IN FIGURE 02. IN AREAS OF GREATER THAN 10-PSF GROUND SNOW LOAD AS DETERMINED BY ASCE 7 OR AHJ, USE SNOW & WIND
COMBINATION RAIL-TO-ROOF
ATTACHMENT SPACING TABLE WWW.GEZELMANPE.COM/GENERIC/PCM.WINDSNOW_US.HTM
· WIND IS THE MAJOR STRUCTURAL CONSIDERATION FOR ROOF-MOUNTED SOLAR EQUIPMENT
THERE SHALL BE TWO PCM RAILS EQUALLY-SPACED UNDER EVERY PV MODULE (ABOUT 25% IN).
PV MODULES MAY BE LANDSCAPE OR PORTRAIT AT CONTRACTOR OPTION. PCM RAILS SHALL RUN PERPENDICULAR TO ROOF FRAMING.
PCM RAILS SHALL BE ATTACHED TO ROOF FRAMING MEMBERS AT DISTANCES NGT (NOT GREATER THAN) CENTER-TO-CENTER DISTANCES
SPECIFIED IN FIGURE 02.
ROOF ATTACHMENT: AT EACH SPECIFIED ANCHOR POINT - A SINGLE CORROSION RESISTANT STEEL (CRS), 5/16” MINIMUM DIAMETER LAG, 3” LONG
IS ACCEPTABLE AT WINDSPEEDS 150 OR LESS. ABOVE THAT, TWO LAGS ARE REQUIRED. A SINGLE, 3/8TH INCH DIAMETER, “J” BOLT IS ACCEPTABLE
ANCHORAGE AT ALL WINDSPEEDS. PV MODULES SHALL ATTACH TO PCM RAILS AT EVERY CROSSING POINT WITH A GSAS MODULE CLAMP OR PCM
CLAMP. ADJOINING MODULES MAY SHARE ATTACHMENT CLAMPS.
S-5 CLAMPS SHALL BE USED ON STANDING SEAM MEATAL ROOFS IN CONJUNCTION WITH PCM RAILS RUNNING PERPENDICULAR TO STANDING
SEAMS. RAIL TO STANDING SEAM CONNECTIONS SHALL BE MADE USING S-5 CLAMPS AT NGT 6-FT S-5 TO S-5 IN PZ1 AND NGT 4-FT S-5 TO S-5 IN PZ-2.
WATERPROOFING; S-5 INSTALLATIONS INVOLVE NO ROOF PENETRATIONS. FOR OTHER ROOFS, LAGGING THRU A GENEROUS PUDDLE OF NOA/PCA
(MIAMI-DADE/FLORIDA) APPROVED ROOFING SEALANT SHALL BE ADEQUATE. CONTRACTOR MAY, WITH APPROVAL OF AHJ, USE ALTERNATE MEANS
& METHODS. CONTRACTOR SHALL ADHERE TO BEST PRACTICES/MEANS & METHODS OF ROOFING CHAPTER OF APPLICABLE BUILDING CODE AND
NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE NO ROOF LEAKS AT SYSTEM START-UP OR AS SYSTEM AGES.
ANY FSEC CERTIFIED
PV MODULE, LANDSCAPE
OR PORTRAIT
WWW.GEZELMANPE.COM/PV/0203P.PCM20_US.PDF (ON PAGE 2)
"SAFE" ALL CASE (ALL WIND SPEED & ALL WIND EXPOSURE CATEGORY) SPACINGS:
S5 PRODUCT CATALOG:
VOID WITHOUT RAISED OR
ELECTRONIC SEAL, MAY NOT BE
USED FOR PLANS ON FILE, EVERY
PERMIT PULLED REQUIRES A SEALED
ELECTRONIC PLAN OR SEALED
ORIGINAL PAPER COPY OF THIS PLAN
ALLEN GEZELMAN
16502 HANNA RD.
LUTZ, FLORIDA 33549
CALCULATED HOLD DOWN SPACINGS MAY BE SEEN AT:
URL REFERENCES
OEM, DATA SHEETS, INSTALLATION MANUALS
HTTP://WWW.S-5.COM/GALLERY/INDEX.CFM
HTTP://WWW.S-5.COM/COMMON/DOWNLOADS/PRODUCTCATALOG_073012.PDF
•
•
•
S5 CLAMP PROFILES:
CLOUDED REVISION TO PROJECT 14-074 UNIVERSAL ENGINEERING SIENCES REVIEW FOR PV
PERMIT. 11556 WILLOW GARDENS DRIVE, WINDERMERE, FL
ROOF PRESSURE ZONE 1 (PZ1) 6 FT CENTER - TO - CENTER +- TO HIT FRAMING
ROOF PRESSURE ZONE 2 (PZ2) 4 FT CENTER - TO - CENTER +- TO HIT FRAMING
ROOF PRESSURE ZONE 3 (PZ3) 2 FT CENTER - TO - CENTER +- TO HIT FRAMING
PH. 813 650 7246
TYP. RIDGE
PZ3
PZ2
Allen@Gezelman PE.COM
www.GezelmanPE.com
PZ3
PROFESSIONAL ENGINEER
WWW.GEZELMANPE.COM/LICENSE.HTML
ITEM 1 DNA (DOES NOT APPLY) PCM PLAN SHEET IS FOR STRUCTURAL ONLY PORTION OF
PROJECT. FSEC CERTIFICATION REQUIREMENT APPLIES ONLY TO ELECTRICAL DESIGN. PCM
PLAN SHEET IS EXEMPT FROM FSEC REVIEW REQUIREMENT.
WIND PRESSURE ZONE DIAGRAM:
HTTP://WWW.GEZELMANPE.COM/REFERENCE/ASCE-7_PRESSUREZONES.PDF
ITEM 2 PV. i CERTIFY THAT THE ROOF TRUSS SYSTEM OF SUBJECT BUILDING WILL WITHSTAND
THE ADDED DEAD / GRAVITY LOAD IMPOSED BY PROPOSED ADDITION.
WIND PRESSURE TABLES:
SLOPE DN
RAFTERS
ROOF LENGTH
HTTP://WWW.S-5.COM/CLAMPS/INDEX_1048.CFM
PCM RAIL
PZ1
PZ2
OFFSET "A"
PCM RAIL
PZ2 PER ASCE 7-10
FIG. 03
HTTP://WWW.GEZELMANPE.COM/GENERIC/WINDPRESSURE.HTM
CALCULATED HOLD DOWN SPACINGS:
WWW.GEZELMANPE.COM/PV/0328S.GS.WILLOWGARDENS_WINDERMERE_FL.PDF
TYP. EAVE
(PAGE 2)
ROOF WIDTH
REFERENCES
REFERENCES ARE ACTIVE LINKS ON PDF VERSION OF THIS PRINT @ WWW.GEZELMANPE.COM/PV/0203P.PCM20_US.PDF
02
DESIGNED PER: ASCE 7-10,2010 IBC & STATE CODES BASED THEREON
AHJ: ANY US JURISDICTION
MODULE: FSEC, SRCC, CEC APPROVED PV MODULE
HOLD DOWN SPACING
SCALE: NTS
03
DESIGN WIND SPEED: 200 MPH
EXPOSURE CATEGORY : D RISK CATEGORY: II
CALCULATION: HTTP://WWW.GEZELMANPE.COM/GENERIC/WINDPRESSURE.HTM
VERIFY
01
PZ3
PZ2
PZ3
WWW.GEZELMANPE.COM/PV/0203P.PCM20_US.PDF (ON PAGE 2)
WIND
JOHN DOE
ANY LOCATION IN THE US
I CERTIFY THAT PV INSTALLATIONS MADE IAW THIS PLAN CAN RESIST POSITIVE & NEGATIVE WIND FORCES PREDICTED IAW ASCE 7-10. THIS IS
ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT.
I CERTIFY THIS DESIGN & SPECIFICATIONS MEET INTERNATIONAL BUILDING CODE (IBC)AND ALL STATE BUILDING CODES BASED UPON IBC
–INCLUDING 2010 FLORIDA BUILDING CODE
ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT TO THE PROVISIONS OF EJCDC
C-700 (ENGINEERS JOINT CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) CURRENT AT THE TIME. THOSE OBJECTING TO SAID EJCDC C-700 OR
PROVISIONS THEREOF ARE DIRECTED NOT TO USE THE AFFIDAVIT, DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON THE PROJECT. EJCDC
C-700 MAY BE VIEWED AT: HTTP://GEZELMANPE.COM/REFERENCE/AG/C-700.PDF
THIS PLAN IS ONLINE FOR REVIEW @
CODE
THIS PLAN SET IS COPY RIGHT PROTECTED AND CONTAINS INTELLECTUAL PROPERTY WHICH BELONGS TO ALLEN GEZELMAN PE.
ACCESS IS GIVEN TO THE INFORMATION HEREON SOLELY FOR THE PURPOSE OF COMPLETION OF THE PROJECT FOR WHICH IT IS INTENDED.
NO OTHER USE MAY BE MADE OF THE INFORMATION, DRAWINGS, OR IDEAS HEREON WITHOUT THE EXPRESS , WRITTEN, PERMISSION OF ALLEN GEZELMAN PE
•
•
•
COPY RIGHT & INTELLECTUAL PROPERTY NOTICE
OWNER:
SAMPLE ROOF LAYOUT PLAN
SCALE: N.T.S. INSTALL ANY LOCATION IN THIS JURISDICTION
CONTRACTOR RESPONSIBLE TO VERIFY THE FIT OF THE PV ARRAY ON APPLICABLE ROOF SLOPE PRIOR TO INSTALLATION.
CONTRACTOR SHALL CONTACT THE ENGINEER IF THE ARRAY MAY NOT FIT AS PROJECTED. CONTRACTOR RESPONSIBLE TO
VERIFY SUN EXPOSURE AND SHADING OF THE PV ARRAY PRIOR TO INSTALLATION!
ALUM CLAMP SYSTEM
PV MODULE
1-1/4"
SOLAR RAIL SYSTEM
WATERPROOF WITH SONNOLASTIC
NP-1 OR EQUAL POLYURETHANE
CAULK
STAR WASHER
ROOF TILE,
FLAT, BARREL ETC.
MOUNTING RAIL
RAILING PCM 2.5 X 0.75
RAILING 2.5 X 0.75
RAIL W/ CLAMP, L-SHAPED
MIN 5 16"-INCH CR ANCHOR
3" EMBEDMENT
RE: ENG. NOTES
EXIST. SHEETING
& MEMBRANE
EXISTING RAFTER
GSAS SOLAR CLAMP ARRAY
ALUM CLAMPS
PV MODULE
SOLAR MOUNT RAIL
3
8
- 16 X 34 HEX HEAD BOLT
3/8-16 FLANGE BOLT
C-C (RE: ENG NOTES)
WATER PROOFING
EXIST. ROOF ASP SHINGLE ROOF
SERRATED L
ROOF MOUNT
RAIL CLAMP ON STANDOFF
STANDOFF W / BASE
STANDOFF
EXIST. ROOF SHEETING
GSAS SOLAR CLAMP
ENLARGED VIEWING & HYPERLINKS:
PRINT VERSION OF THIS PLAN PROVIDES MINIMUM INFORMATION NEEDED BY USERS.
ELECTRONIC VERSION (EV) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES HYPERLINK
ACCESS TO OEM MANUALS AND ABUNDANT OTHER SUPPLEMENTARY INFORMATION.EV MAY BE
ACCESSED AT: WWW.GEZELMANPE.COM/PV/ 0328S.GS.WillowGardens_Windermere_FL.dwg
GSAS END CLAMP
07
STAINLESS STEEL ELECTRICAL BONDING
'STAR' WASHER
APPROVED ROOF ATTACHMENT W/ (GSAS) GEZELMAN SOLAR ANCHOR SYSTEM
SCALE: NTS
3/8" CRS. BOLT, W/ MIN 3"
THREAD EMBEDMENT IN BLOCKING,
PURLIN,JOIST OR TRUST
BLOCKING,TRUSS,
RAFTER OR PURLIN
SYSTEM:
APPROVED PCM ROOF MOUNTING DETAILS
06
ANY JURISDICTION IN THE US
ALUM L-FOOT
GSAS SOLAR CLAMP, MID FIELD
INSTALLATION OF A ROOF MOUNT
1-1/2"
CONTACT DESIGN TEAM @
www.GezelmanPE.com
L FOOT BRACKET
LENGTH AS NEEDED
PCM PRECISION AND S.L. PLOTA
SCALE: 3" = 1'-0"
6203 80TH AVENUE N
PINELLAS PARK FL 33781
USA
GSAS CLAMP
PV MODULE
PV MODULE
3
3
8 - 16 X 4 HEX HEAD BOLT
3/8-16 FLANGE BOLT
PV MODULE
PV MODULE, MID CLAMP
PV MODULE
C-C (RE: ENG NOTES)
S5
EXIST. STANDING SEAM METAL ROOF
RAIL CLAMP 2.5", 3"
PH. 727-547-6277
FAX 727-547-6279
SOLAR MOUNTING RAIL
SOLAR MOUNTING RAIL
SERRATED L
ROOF MOUNT
RAIL CLAMP 7"
PZ1 6'-0"
S5
PUBLISHED:
REVISIONS:
PZ2 4'-0"
SET SCREW, TORQUE PER OEM
PZ3 2'-0"
EXIST. ROOF SHEETING
S5
EXISTING TOP CHORD OF TRUSS / RAFTER
C-C MAX. 24"
04
MODEL/APPEARANCE OF S-5 VARIES W/APPLICATION
SEE S-5 FIG. 01 FOR REFERENCES
S5
C-C MAX. 24"
S5
C-C MAX. 24"
APPROVED ROOF ATTACHMENT SYSTEM W/ S5 CLAMPS
S5 CLAMP SYSTEM C-C SPAN DIAGRAM
SCALE: NTS
SCALE: NTS, APPROVED UNDER THIS PERMIT
C-C MAX. 24"
SHEET NAME:
S5
DRAWN: SB
PV MODULE , END CLAMP
05
RAIL SPLICE
GROUNDING CLIP
PCM RACKING COMPONENTS APPROVED UNDER THIS PERMIT
SCALE: NTS
SHEET NO:
CHECKED: AG
CALCULATED HOLD DOWN SPACINGS
NOTICE TO AHJ, CONTRACTORS, OIP (OTHER INTERESTED PARTIES) THESE SPECIFICATIONS ARE PART & PARCEL OF MY SEALED PCM PV INSTALLATION PLANS
SPECS MUST BE ON OR ACCOMPANIED BY SIGNED & SEALED PLAN TO BE VALID
PCM 2.5 X 0.75 rail calculations
2010 FBC ASCE 7-10
mid collector height 20' or less
roof pressure zone 1
all roof slopes
design wind speed
max. allow. c-c attachment inches
exp B
exp C
exp D
200
64
56
51
190
67
59
54
180
71
62
57
175
HVHZ
n/a
64
58
170
75
66
60
160
80
70
64
150
85
75
68
140
91
80
73
130
98
86
79
120
106
94
86
110
116
102
93
RAFTER CLIPS & 2"X4"X12" MIN BLOCKING IN LIEU OF ROOF FRAMING ATTACHMENT OK
Use heavy bead liquid nails min 12" framing to sheeting joints bracketing blocking
mid collector height 20' or less
roof pressure zone 2
all roof slopes
design wind speed
max. allow. c-c attachment inches
exp B
exp C
exp D
200
47
42
38
190
50
44
40
180
53
46
42
175
HVHZ
n/a
48
43
170
56
49
45
160
59
52
48
150
63
56
51
140
68
60
54
130
73
64
59
120
79
70
64
110
86
76
68
RAFTER CLIPS & 2"X4"X12" MIN BLOCKING IN LIEU OF ROOF FRAMING ATTACHMENT OK
Use heavy bead liquid nails min 12" framing to sheeting joints bracketing blocking
INSTALLATION IN ROOF PRESSURE ZONE 3 REQUIRES SITE-SPECIFIC ENGINEERING
PZ3 SHALL NOT BE USED IN HVHZ